4
Interface information
4.1 BACnet interface
Application
The expansion module EM-IP supports the following
BACnet interface functions in the BACnet-IP protocol
settings:
Native BACnet, i.e. the BACnet interface is imple-
mented on the field module (EASYLAB volume flow
controller)
External hardware components such as physical
gateways are not required
BACnet interface documentation includes the fol-
lowing documents: Protocol Implementation Con-
formance Statement (PICS), BACnet Interoperability
Building Blocks Supported (BIBBS), as well as a
description of the device object and the supported
objects
Abbreviations
EASYLAB:
FH
- Fume cupboard controller
RR
- Room controller for supply air or extract air
(RS, RE, PC)
RR RMF - Room controller with active room manage-
ment function
EC, SC
- Single controller for supply air or extract air
(EC, SC)
TAM
- Adapter module
TAM
RMF
- Adapter module with active room manage-
ment function
WR
- Defaults for the volume flow controller or
room, from the central BMS
RD
- Data provided by the volume flow con-
troller or room
TROX UNIVERSAL CONTROLLER:
RS/RE
- Volume flow controllers for supply or
extract air
RS/RE
RMF
- Volume flow controller with active room
management function
PR*/PD*
- Room pressure controller or duct for
supply or extract air
PR*/PD*
RMF
- Room pressure controller or duct with
active room management function
See also the PICS list for EM-IP under ‘Help’ in the
web server
Chapter 3.5.8 ‘Functions of the ‘Help’
Interface information
BACnet interface
Expansion module EM-IP
26