CVHH-SVX001A-EN
75
Start-up and Shut-dow n
This section w ill provide basic inform ation on chiller
operation for com m on events. With m icroelectronic
controls, ladder diagram s cannot show today’s com plex
logic, as the control functions are m uch m ore involved
than older pneum atic or solid state controls.
Chiller Sequence of Operation
Adaptive control algorithm s can also com plicate the exact
sequence of operation. This section illustrates com m on
control sequences.
Software Operation Overview Diagram
Figure 41
is a diagram of the five possible software states.
This diagram can be thought of as a state chart, w ith the
arrow s, and arrow text, depicting the transitions betw een
states.
Descriptions
•
The text in the circles are the internal software
designations for each state.
•
The first line of text in the circles are the visible top
level operating m odes that can be displayed on Tracer
AdaptiView.
•
The shading of each software state circle corresponds
to the shading on the tim e lines that show the state that
the chiller is in.
Figure 41.
Software operation overview
Stopping
Preparing to Shut Down
Shutting Down
Running
Running
Running - Limit
Stopped
Stopped
Run Inhibit
Starting
Auto
Waiting to Start
Starting Compressor
Start
Command
Diagnostic
Reset
Confirmed Start
Stop Command
Diagnostic
Confirmed Shutdown
Power
Up
Fast Restart or Satisfied Setpoint
Stop Command or Diagnostic