Installation: Controls
42
CVHH-SVX001A-EN
Communication Interfaces
There are four connections on the UC800 that support the
com m unication interfaces listed. Refer to
Figure 26, p. 41
for the locations of each of these ports.
•
BACnet M S/TP
•
M ODBUS Slave
•
LonTalk using LCI-C (from the IPC3 bus)
•
Com m 4 using TCI (from the IPC3 bus)
Rotary Sw itches
There are three rotary sw itches on the front of the UC800
controller. Use these sw itches to define a three-digit
address w hen the UC800 is installed in a BACnet or
M ODBUS system (e.g., 107, 127, etc.).
N ot e: Valid addresses are 001 to 127 for BACnet and 001
to 247 for M ODBUS.
LED Description and Operation
There are 10 LEDs on the front of the UC800.
Figure 27
show s the locations of each LED and
Table 11, p. 42
describes their behavior in specific instances.
Im port ant :
M aintain at least 16 cm (6 in.) betw een low-
voltage (<30V) and high voltage circuits.
Failure to do so could result in electrical
noise that could distort the signals carried
by the low-voltage w iring, including IPC.
1.
Rotary Sw itches for setting BACnet
®
M AC address or M ODBUS
®
ID.
2.
LINK for BACnet M S/TP, or M ODBUS Slave (tw o term inals, ±). Field
w ired if used.
3.
LINK for BACnet M S/TP, or M ODBUS Slave (tw o term inals, ±). Field
w ired if used.
4.
M achine bus for existing m achine LLIDs (IPC3 Tracer bus 19.200 baud).
IPC3 Bus: used for Com m 4 using TCI or LonTalk
®
using LCI-C.
5.
Pow er (210 m A at 24 Vdc) and ground term inations (sam e bus as
item 4). Factory w ired.
6.
Not used.
7.
M arquee LED pow er and UC800 Status indicator (
Table 11, p. 42
).
8.
Status LEDs for the BAS link, M Bus link, and IM C link.
9.
USB device type B connection for the service tool (Tracer TU).
10. The Ethernet connection can only be used w ith the Tracer AdaptiView
display.
11.
USB Host (not used).
Figure 26.
Wiring locations and connection ports
Bot t om View
10
11
Figure 27.
LED locations
Table 11.
LED behavior
LED
U C8 0 0 St a t u s
Mar quee LED
Pow e r e d. I f t he Mar quee LED is green solid, t he
UC800 is pow er ed and no pr oblem s ex ist .
Low pow e r or m a lf u n ct ion . I f t he Mar quee LED is
red solid, t he UC800 is pow er ed, but t her e ar e
pr oblem s pr esent .
Ala r m . The Marquee LED blink s Red w hen an alar m
exist s.
LI NK, MBUS,
I MC
The TX LED blink s green at t he dat a t ransfer rat e
w hen t he UC800 t ransfer s dat a t o ot her dev ices on
t he link .
The Rx LED blink s yellow at t he dat a t ransfer rat e
w hen t he UC800 receives dat a fr om ot her dev ices on
t he link .
Et her net Link
The LI N K LED is solid gr een if t he Et her net link is
connect ed and com m unicat ing.
The ACT LED blink s yellow at t he dat a t ransfer rat e
w hen dat a flow is act ive on t he link.
Ser v ice
The Ser vice LED is solid green w hen pressed. For
qualified serv ice t echnicians only. Do not use.
LINK
LINK
MBUS
IMC
TX
RX
ACT
SERVICE
Mar quee LED