System Control Circuit Wiring (Field Wiring)
CVHH-SVX001A-EN
65
1.
With factory-installed ifm efector flow-sensing
devices, a secondary field-provided flow-sensing
device is optional. When a secondary flow-sensing
device is used, rem ove the factory jum per, and install
its contacts betw een 1X1-5 to 1K27-4; this places the
secondary flow sensing device in series w ith the
ifm efector.
2. For field-provided prim ary proof of flow devices,
connect the prim ary proof of flow device betw een
term inals 1X1-6 to 1K16-J2-2. The secondary field
provided flow sensing device is optional; how ever,
w hen it is present, it m ust be field-w ired in series w ith
the prim ary proof of flow device.
Temperature Sensor Circuits
All tem perature sensors are factory installed except the
optional outdoor air tem perature sensor (refer to
Figure 33, p. 65
for sensor locations). This sensor is
required for the outdoor air tem perature type of chilled
water reset. Use the follow ing guidelines to locate and
m ount the outdoor air tem perature sensor. M ount the
sensor probe w here needed, how ever, m ount the sensor
m odule in the control panel.
Figure 33.
CVHH sensor locations
1 . Tracer Adapt iView display m odule
2 . Mot or w inding t em perat ure 1
3 . Mot or w inding t em perat ure 2
4 . Mot or w inding t em perat ure 3
5 . Oil pum p dischar ge pr essure t ransducer
6 . Oil t ank pr essure t ransducer
7 . Evaporat or w at er differ ent ial pr essur e t ransducer
8 . Condenser w at er differ ent ial pr essur e t ransducer
9 . Com pr essor discharge refrigerant t em perat ur e sensor
1 0 .Evaporat or sat urat ed r efr igerant t em perat ur e sensor
1 1 .Condenser sat urat ed refrigerant t em perat ur e sensor
1 2 .Second condenser ent ering wat er t em perat ure sensor ( used on HTRC)
1 3 .Second condenser leaving wat er t em perat ure sensor ( used on HTRC)
1 4 .Oil t ank t em perat ur e sensor
1 5 .Evaporat or ent er ing wat er t em perat ur e sensor
1 6 .Evaporat or leav ing w at er t em perat ur e sensor
1 7 .Condenser ent er ing w at er t em perat ur e sensor
1 8 .Condenser leav ing w at er t em perat ur e sensor
1 9 .I nboar d bear ing t em perat ur e sensor
2 0 .Out board bearing t em perat ure sensor
2 1 .Oil cooling solenoid valve
2 2 .I nlet guide vane fir st st age act uat or
2 3 .I nlet guide vane second st age act uat or
2 4 .Out board bearing pad t em perat ur e sensor 1
2 5 .Out board bearing pad t em perat ur e sensor 2
2 6 .Out board bearing pad t em perat ur e sensor 3
2 7 .Condenser high pr essur e cut out swit ch
2 8 .Condenser refr igerant pr essure t ransducer
2 9 .Oil t ank vent line valve
2
=
4
0
p
1
3
9
7
w
q
5
ty
er
ty
ty
er
er
8
] a
\
See Det ail A
See Det ail B
Det ail A
Det ail B
ty
er
=q
[
u
o
f
6
sd
-
i
Summary of Contents for CVHH
Page 110: ......