Power Supply Wiring
58
CVHH-SVX001A-EN
Terminal Clamps
N ot e: Graphic labels (show n above) are used for CE
application only.
Im port ant :
•
Before servicing, disconnect all pow er sources and
allow at least 30 m inutes for capacitors to discharge.
•
All electrical enclosures—unit or rem ote—are IP2X.
Term inal clam ps are supplied w ith the m otor term inals to
accom m odate either bus bars or standard m otor term inal
w ire lugs. Term inal clam ps provide additional surface area
to m inim ize the possibility of im proper electrical
connections.
Wire Terminal Lugs
Wire term inal lugs m ust be field supplied.
•
Use field-provided, crim p-type w ire term inal lugs
properly sized for the application.
N ot e: Wire size ranges for the starter line and load-
side lugs are listed on the starter subm ittal
draw ings supplied by the starter m anufacturer
or Trane. Carefully review the subm itted w ire
lug sizes for com patibility w ith the conductor
sizes specified by the electrical engineer or
contractor.
•
On 600 V and below, a term inal clam p w ith a
9.525-m m (3/8-in.) bolt is provided on each m otor
term inal stud; use the factory-supplied Belleville
washers on the w ire lug connections.
Figure 32
illustrates the junction betw een a m otor term inal stud
and term inal lug.
•
Torque for this assem bly is 32.5 N·m (24 ft·lb).
•
Install but do not connect the pow er leads betw een the
starter and com pressor m otor. (These connections w ill
be com pleted under supervision of a qualified Trane
service engineer after the pre-start inspection.)
Bus Bars
Bus bars and extra nuts are available as a Trane option.
Install the bus bars betw een the m otor term inals w hen
using a starter that is:
•
a low-voltage AFD
•
across-the-line
•
prim ary reactor/resistor
•
auto transform er
•
custom er-supplied
NOTICE:
Use Copper Conductors Only!
Failure to use copper conductors could result in
equipment damage as unit terminals are not designed
to accept other types of conductors.
X39003892001A
Figure 32.
Terminal stud, clamp, and lug assembly
(600 V and below )
1.
Belleville w asher
2.
Term inal lugs
3.
Term inal clam p
4.
M otor term inal stud
5.
Term inal m ounting bolt
NOTICE:
Component Damage!
Failure to ensure the power supply w iring and output to
motor w iring are connected to the proper terminals.
could cause catastrophic failure of the starter and/ or
motor.
2
1
3
4
5