K-2
E6581531
11
1. Basic parameter [2/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f
Reference
RV
0015
V/f control mode selection
0:Constant torque characteristics
1:Voltage decrease curve
2:Automatic torque boost
3:Sensorless vector control 1 (speed)
4:-
5:V/f 5-point setting
6:PM control
7:PG feedback control
8:-
9:Energy-saving
10:Advanced energy-saving
1/1
0 0 0
Disabled
-/-
-/-
●
/-
●
/-
-
-/-
-/-
-/
●
-
●
/-
●
/-
●
●
-
-
-
●
-
-
-
-
-
5. 6
XD
0016
Manual torque boost 1
0.0~30.0%
0.1/0.1
*1 *1 *1
Enabled
-
●
5.
7
XN
0014
Base frequency 1
25.0~500.0Hz
0.1/0.01
50.0
60.0
50.0
Disabled
●
/
●
●
5.
8
XNX
0409
Base frequency voltage 1
50~990V
1/0.1
500
575 690
Disabled
●
/
●
●
5.
8
HJ
0011 Maximum
frequency
30.0~500.0Hz
0.1/0.01
80.0
80.0
80.0
Disabled
●
/
●
●
5.
9
WN
0012 Upper
limit
frequency
0.0~
HJ
Hz
0.1/0.01
50.0
60.0
50.0
Enabled
●
/
●
●
5.
10
NN
0013 Lower
limit
frequency
0.0~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
10
CEE
0009
Acceleration time 1
0.1~6000 sec.
0.1/0.1 *2
*1 *1 *1
Enabled
●
/
●
●
5.
2
FGE
0010
Deceleration time 1
0.1~6000 sec.
0.1/0.1 *2
*1 *1 *1
Enabled
●
/
●
●
5.
2
CXH
0213
RR/S4 input point 2 frequency
0.0~
HJ
Hz
0.1/0.01
50.0
60.0
50.0
Enabled
●
/
●
●
5.
11
CKH
0204
VI/II input point 2 frequency
0.0~
HJ
Hz
0.1/0.01
50.0
60.0
50.0
Enabled
●
/
●
●
5.
11
UT
0018
Preset speed operation frequency 1
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
UT
0019
Preset speed operation frequency 2
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
UT
0020
Preset speed operation frequency 3
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
UT
0021
Preset speed operation frequency 4
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
UT
0022
Preset speed operation frequency 5
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
UT
0023
Preset speed operation frequency 6
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
UT
0024
Preset speed operation frequency 7
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
5.
12
HT
0008
Forward run/reverse run selection
(operation panel operation)
0:Forward run
1:Reverse run
2:Forward run (Forward/reverse switchable on
operation panel)
3:Reverse run (Forward/reverse switchable on
operation panel)
1/1
0 0 0
Enabled
●
/
●
●
5.
13
*1: Default values vary depending on the capacity.
⇒
See the table of K-47.
*2: Changing the parameter
VR
enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
*3: Inverter with a model number ending with -WN: 60.0 -WP: 50.0