E6581531
E-24
5
H
=
(Estimation of temperature)
This parameter adjusts automatically overload protection, predicting the inverter internal temperature rise.
(diagonally shaded area in the figure below)
60
100%: Inverter rated output current
time
[s]
Monitored output current [%]
0
110%
120%
Inverter overload protection characteristics
Note 1: If the load applied to the inverter exceeds 120% of its rated load or the operation frequency is less than
0.1Hz, the inverter may trip (
QN
or
QER
~
QER
) in a shorter time.
Note 2: The inverter is factory-set so that, if the inverter becomes overloaded, it will automatically reduce the
carrier frequency to avoid an overload trip (
QN
or
QER
~
QER
). A reduction in carrier frequency
causes an increase in noise from the motor, but this does not affect the performance of the inverter.
If you do not want the inverter to reduce the carrier frequency automatically, set the parameter
H
=
.