E6581531
E-6
5
This setting is used to set the frequency using the operation panel and to perform operation control using the terminal
board.
Use the and keys to set the frequency.
In sink logic mode: PWR-P24/PLC ON: Standby (ON (short-circuited) by default),
F-CC ON: Forward run, R-CC ON: Reverse run.
This setting is used to set the frequency and to perform operation control, using the operation panel.
Use the and keys to set the frequency.
Use the and keys to perform operation control.
This setting is used to coast and stop the motor by means of an S3 terminal signal.
The frequency is adjusted according to the setting of the parameter
HOQF
. The motor is operated in accordance with the
setting of the parameter
EOQF
.
If S3 and CC are short-circuited, the motor will be put into a standby state. If the circuit between S3 and CC is opened, the
motor coasts and stops.
5.5
Selection of operation mode
EOQF
: Command mode selection
HOQF
: Frequency setting mode selection 1
<Command mode selection>
[Parameter setting]
Title
Function
Adjustment range
Default setting
EOQF
Command
mode selection
:Terminal input enabled
:Operation panel input enabled (including LED/LCD option input)
:2-wire RS485 communication input
:4-wire RS485 communication input
:Communication option input
[Programmed value]
:
Terminal board operation
ON and OFF of an external signal Runs and stops operation.
:
Operation panel operation
Press the and keys on the operation panel to Run and stop
a run. (including LED/LCD option input)
:
2-wire RS485 communication operation
Run and stop commands are entered from the 2-wire
RS485 communications device.
(Communication No.: FA00)
:
4-wire RS485 communication operation
Run and stop commands are entered from the 4-wire
RS485 communications device.
(Communication No.: FA04)
:
Communication option input enabled
Signals from an optional communication device are used to
start and stop operation.
⇒
For details, refer to Instruction Manual (E6581281,
E6581343, E6581288) specified in Section 6.36.
* There are two types of function: the function that conforms to commands selected by
EOQF
, and the
function that conforms only to commands from the terminal board.
⇒
Refer to the table of input terminal function selection in Section 7.2.
* When priority is given to commands from a linked computer or terminal board, they have priority over the setting of
EOQF
.
Frequency setting and operation with operation panel (
CW
=
)
• Function
These parameters are to program which command to the inverter (from operation panel, terminal board, remote
input device or options) will be given priority in running/stopping the operation and in frequency setting (speed).
RUN
STOP
RUN
STOP
Frequency setting with operation panel and operation with terminal board
Coast stop (
CW
=
)