![Toshiba TOSVERT VF-PS1 Instruction Manual Download Page 28](http://html.mh-extra.com/html/toshiba/tosvert-vf-ps1/tosvert-vf-ps1_instruction-manual_424777028.webp)
E6581531
A-16
1
Example of wiring of each model
Caution
Prohibited
IMPROPER
WIRING
PRACTICES
Making a connection inappropriate for the line voltage will damage the transformer(s) and the VFPS1.
Failure to follow this instruction can result in injury and/or equipment damage.
Each transformer features one 500V/600V connector and one 690V connector. Connect the connector appropriate
for the line supply (see above). Set the unused connector to the parked position.
VFPS1-6500KPC to 6630KPC drives feature 2 transformers. Make this connection for each transformer.
VFPS1-6110KPC to 6200KPC
VFPS1-6250KPC to 6400KPC
VFPS1-6500KPC to 6630KPC
Location of transformers:
690V/50Hz line
Set X2A to X0 (Parked position)
Set X2B to X2 (In-use position)
Connection of a transformer
500V/50Hz or 600V/60Hz line
Set X2B to X0 (Parked position)
Set X2A to X2 (In-use position)
X0
X2B
Parked position
In-use position
X2A
X2
X0
X2A
Parked position
In-use position
X2B
X2
Transformer
Transformer