E6581531
F-49
6
failure.
Note 2: When using a single-phase direct current to operate the inverter, disable this function (
H
=
)
6.26.8 Control mode for low current
H
: Low current detection hysteresis width
H
: Low current trip selection
H
: Low current detection current
H
: Low current detection time
• Function
If the current is lower than
H
level and passes for a time longer than
H
, the inverter trips.
Trip information is displayed as “
WE
.”
H
=
: No tripping (Failure signal FL deactivated).
A low current alarm can be put out by setting the output terminal function selection parameter.
H
=
: The inverter will trip (the failure signal FL will be activated) if a current below the current set with
H
flows for the period of time specified with
H
.
Title
Function
Adjustment range
Default setting
H
Low current detection hysteresis width
~
%
H
Low current trip selection
: No trip
:Trip
H
Low current detection current
~
%
H
Low current detection time
~
sec.
<Example of operation>
Output terminal function: 26 (UC) Low current detection
H
=
(No trip)
Ex.) When outputting low current detection signals through output terminal OUT1
Title
Function
Adjustment range
Example of setting
H
Output terminal function selection 1(OUT1)
~
Note: To put out signals to the terminal OUT2, select the parameter
H
.
Time [sec]
H
+
H
H
Output current [%]
Low current
signal output
H
ON
OFF
OFF
less than
H
When
H
=
(tripping), the inverter will trip if low current lasts for the period of time set with
H
.
After tripping, the low current signal remains ON.