[25] Operation panel parameters [1/3]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f
Constant
Reference
H
0700
Parameter write protect selection
0:Permit
1:Prohibit
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 1
FURW
0701
Current/voltage unit selection
0:%
1:A (ampere)/V (volt)
1/1
0
0
0
Enabled
●
/
●
●
5. 15
H
0702
Frequency free unit display magnification 0.00:OFF, 0.01~200.0
0.01/0.01
0.00
0.00
0.00
Enabled
●
/
●
●
6. 31. 2
H
0703
Frequency free unit conversion selection
0:All frequencies display free unit conversion
1:PID frequencies free unit conversion
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 2
H
0705
Free unit display gradient characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1
1
1
1
Enabled
●
/
●
●
6. 31. 2
H
0706
Free unit display bias
0.00~
HJ
Hz
0.01/0.01
0.00
0.00
0.00
Enabled
●
/
●
●
6. 31. 2
H
0707
Changing step selection 1
0.00:Disabled, 0.01~
HJ
Hz
0.01/0.01
0.00
0.00
0.00
Enabled
●
/
●
●
6. 31. 3
H
0708
Changing step selection 2
0:Disabled, 1~255
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 3
H
0709
Standard monitor hold function
0:Real time
1:Peak hold
2:Minimum hold
1/1 0 0 0
Enabled
●
/
●
●
8.
3
H
0710
Standard monitor display selection
0~80 *1
1/1
0 0 0
Enabled
●
/
●
●
8.
3
H
0711
Status monitor 1 display selection
Ditto
1/1
1 1 1
Enabled
●
/
●
●
8.
3
H
0712
Status monitor 2 display selection
Ditto
1/1
2 2 2
Enabled
●
/
●
●
8.
3
H
0713
Status monitor 3 display selection
Ditto
1/1
3 3 3
Enabled
●
/
●
●
8.
3
H
0714
Status monitor 4 display selection
Ditto
1/1
4 4 4
Enabled
●
/
●
●
8.
3
H
0721
Operation panel stop pattern selection
0:Deceleration stop
1:Coast stop
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 5
H
0730
Operation panel frequency setting
prohibition selection
0:Permit
1:Prohibit
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 1
H
0734
Operation panel emergency stop
operation prohibition selection
0:Permit
1:Prohibit
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 1
H
0735
Operation panel reset operation
prohibition selection
0:Permit
1:Prohibit
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 1
H
0736
Prohibition of change of
EOQF
/
HOQF
during operation
0:Permit
1:Prohibit
1/1
1 1 1
Enabled
●
/
●
●
6. 31. 1
H
0737
All key operation prohibition
0:Permit
1:Prohibit
1/1
0 0 0
Enabled
●
/
●
●
6. 31. 1
This parameter moves to a fundamental parameter.
*1:
⇒
For the adjustment range, see the table on page K-38.