8.2
Starting/Stopping-Remote Control
The remote STARTING/STOPPING possibilities are identified in the following
figure and table.
8 - 5
START/STOP Terminals Connections
ST
F
R
CC
F
R
ST
Remote START/STOP Connections Possibilities
Terminal Connection
Action
ST-CC
F-CC
R-CC
OFF
ON/OFF
ON/OFF
The inverter is OFF. OFF will be displayed. If running
when ST-CC is broken the motor will coast to a stop.
ON
OFF
OFF
The inverter is ON but not running.
ON
ON
OFF
The inverter is ON and will run in a FORWARD direction if an
input signal is applied.
ON
OFF
ON
The inverter is ON and will run in a REVERSE direction if an
input signal is applied.
ON
ON
ON
Same as REVERSE connection above.
ON = short circuit
OFF = open circuit
Note:
1)
With ST-CC (ON), switching F-CC or R-CC (OFF) will cause the motor to decelerate to
a stop.
2)
If input power is turned off (with MCCB) while inverter is running, the motor will coast to
a stop.
3)
Acceleration and Deceleration rates are determined by the preset values of 1st
Function #2 (ACC/DEC).
4)
When switching from a forward run to a reverse run the motor will decelerate to a stop,
then accelerate in the reverse direction.
CAUTION
Avoid using the input power switch (MCCB) to start and
stop the inverter. Use for an emergency stop only
.