TOSHIBA
#2 output frequency
0 to Max. frequency
Hz
80
8-23
RR terminal priority
0: IV terminal input "on"
0
8-23
1: RR terminal input "on"
5
#1 output frequency
0 to Max. frequency
Hz
0
8-23
8.4.2
Terminal IV
Terminal IV ( ) is a special terminal which is used in conjunction with
1st Function key
#5
to output exact frequencies based upon specific input
reference signals. These output frequencies do not necessarily have a one-to-
one ratio with the input reference signals. The following graphs and examples
illustrate how this function can be adjusted.
8 - 13
IV
CC
Hz
100%
5Vdc
20mAdc
5Vdc
10Vdc
JP1=V
JP1=I
JP2=5V
JP2=10V
0%
0V
0mA
0V
0V
4mA
20%
IV
IV
REF
REF
Max Frequency
(FH) and/or (F-P2)
IV-ref. setting point #1
0 to 100
%
20
8-23
IV-ref. setting point #2
0 to 100
%
100
8-23
Function Function
Adjustment
Factory
Error
Ref.
No.
Name
Display
Range
Unit
Set
Message
Page
Function Parameters
0Hz (F-P1)
Factory Setting
% INPUT SIGNAL
Example:
Application requiring the following output characteristics is shown below:
20
(F-P1)
60
(F-P2)
FH 80
Hz
P1=50% of maximum input signal
F-P1=20Hz
P2=80% of maximum input signal
F-P2=60Hz
FH=80Hz
35%
50%
(P1)
80%
(P2)
95% 100%
Input Signal
In the above graph the inverter has no output frequency until the input signal has reached 35%
of its maximum. This is due to the linear characteristics of the IV Function. Also notice that the
maximum frequency is reached before 100% of the input signal is applied.
Note:
In most cases the value of UL is less than FH.The value of UL cannot be greater than FH.
(F-P2) 60
(F-P1) 40
In the above graph the inverter has an output frequency of
20Hz even with a 0% input signal. Also notice that the
maximum output frequency is never reached unless the input
signal goes above 100%. (i.e. a 7Vdc input signal is consid-
ered a 140% input signal when using a 0~5Vdc input.
FH
20
33%
0(P2)
100%(P1)
66%
In the above graph the inverter has a negative output. In
other words, as the input signal increases the output
frequency decreases. Notice that at 0% and 100% input
the inverter outputs 60Hz and 0Hz, respectively.
Hz
Input
Signal
FH 80
(F-P2) 60
(F-P1)40
20
40%(P1)
80%(P2) 100%
0
Hz