Smart Manager
Engineering Book
34
-EN
1
ON
OFF
2 3 4 5 6 7 8
DS24
<4> Always
OFF
Always set this bit to OFF.
<5> Control group Selection line
OFF: LINE 1
ON: LINE 2
* Set a line number for which the control group selection is used.
Factory setting: All OFF
CENTRAL 1:Disables operation start / stop using the remote controller.
CENTRAL 2:Disables operation start / stop, operation mode switching, and temperature setting using the remote
controller.
Switch No.
<1>
<2>
<3>
Central controller operation
Timer
OFF
→
ON
Timer
ON
→
OFF
(1)
All ON
All OFF
OFF
OFF
OFF
(2)
No change
All OFF
ON
OFF
OFF
(3)
All indoor units are locally
controllable.
All indoor units CENTRAL 1
OFF
ON
OFF
(4)
All OFF and all indoor units to
be CENTRAL 1
ON
ON
OFF
(5)
All indoor units CENTRAL 2
OFF
OFF
ON
(6)
All OFF and all indoor units to
be CENTRAL 2
ON
OFF
ON
<6> Control group selection enable
OFF: Normal mode
ON: Control group selection
Set this bit to ON when the control group selection is used.
* To use the control group selection, set DS23-<2> to <5> and DS24-<5>
to <6>.
<7> Buzzer
OFF: With buzzer sound
ON: Without buzzer sound
<8>
indication
OFF: Displayed
ON: Not displayed
<1> to <3> Timer input switching
These bits switch operation when the weekly timer has changed.
• Use (1) and (2) only in the remote control mode.
• When the control group selection is used, “All ON,” “All OFF” and
“all indoor units” mean those within the set group range.
<DS24>