Connections to external equipment
Example of connection to external equipment which is connected to Digital Input/Output connector.
Designation
Input /
Output
item
Central Controller side
External equipment side
Input / output
conditions
Terminal name
Example of circuit
Input / output
conditions
DO1
(Alarm output)
DO2
(Run output)
DO-COM
(Output
common)
Status
output
Allowable
terminal voltage
/ current
DC24 V / 35 mA
Wiring length:
100 m or less
DI1
(All stop input)
DI2
(All start input)
DI3
(Fire alarm
input)
DI-COM
(Input
common)
Control
input
Non-voltage A
contacts
Pulse or static
* Non-voltage
contacts must
be compatible
with minimal
current.
DC5 V / 3 mA
Pulse width:
300 ms or more
Wiring length:
100 m or less
N
L
35
55
35
55
35
6
Length of stripped power cable
Length of stripped TCC-LINK
communication cable
Length of stripped Digital Input/
Output communication wire
Attach the supplied clamp filter to the LAN cable.
* Wind the LAN cable around the clamp filter as shown
below when attaching the filter to the cable. After
attaching the filter, fix it to the LAN cable using a
supplied cable tie.
* Attach the clamp filter as near the main unit as possible.
LAN cable
Loosen the screw with the screw
driver, insert the Digital Input/Output
communication wire, then tighten
the screw again to fix the wire firmly.
Round pressure
terminal
Attach a round pressure terminal to
the end of each wire of the power
cable, communication cable and
power cable for central controller.
35
Length of stripped RS-485
communication cable
DO1
DO2
DO-COM
Digital
output
5V
5V
5V
DI1
DI2
DI-COM
DI3
Pulse or static
Pulse or static
Static