Smart Manager
Engineering Book
14
-EN
4-2. Installation of the Smart Manager
4-2-1. Smart Manager
Confirm all the parts on the list below are supplied.
Part name
Part name
Quantity
Remarks
1
Central Controller
1
2
Power unit
1
3
Installation Manual
Owner’s Manual
Network Configuration Guide
11
11 languages
English, French, German, Italian, Spanish, Portuguese,
Greek, Dutch, Russian, Turkish, Chinese.
4
CD-R
1
5
Clamp filter
1
6
Cable tie
1
For fixing the clamp filter
7
Screws
8
4 for fixing the central controller
4 for fixing the power unit
8
Brackets
2
For combining the central controller and power unit.
9
Bracket screws
4
For combining the central controller and power unit.
No.
Line
Type / Wire size / Length
1
For TCC-LINK
2-core shield wire
1.25 mm², 1000 m max. (total length including
2.00 mm², 2000 m max. air conditioner area)
2
For RS-485
2-core shield wire
1.25mm², 500m max. (total length)
For power
(220 - 240 V AC)
H05RN-F or 245IEC57
0.75 mm², 50 m max.
For Digital Input/Output connection
2-core wire
0.3 mm², 100 m max.
For power supply
(Between the power unit and central controller)
4-core wire
0.75 mm², 20 m max.