56
9-3. Troubleshooting
Main remote controller (NRC-01HE)
(1) Checking
When an error occurred in the Air to Air Heat
Exchanger with DX Coil Unit, the check code and
the unit No. of Air to Air Heat Exchanger with DX
Coil Unit appear on the display part of the remote
controller.
The check code is only displayed during the
operation.
If the display has disappeared, follow “Checking the
error history” below to check.
(2) Checking the error history
When an error occurred in the Air to Air Heat Exchanger with DX Coil Unit, the error history can be checked in the
following procedure. (Up to 4 errors are stored.)
The error history can be checked even while the unit is running or stopped.
<Procedure>
Perform while the unit is stopped.
1
Press and hold the
button for 4
seconds or longer to enter the service check
mode.
The service check lights up. The CODE No. "
" and
latest alarm appear. The alarmed UNIT No. and its
content appear.
2
To monitor other error history, press the
buttons to change the error history No. (CODE
No.).
CODE No. "
" (Latest)
ĺ
CODE No. "
" (Old)
Note:
Up to 4 errors are stored.
3
Press the
button to return the display to
normal.
REQUIREMENT
Do not press the
button as it will erase the entire error history of the indoor unit.
How to read the code display
Check code
Unit No. of the Air to
Air Heat Exchanger
with DX Coil Unit
with a problem
Procedure
Return the display to normal.
<7-segment display>
<Actual character>