Control outline
Indoor unit (Air to Air Heat Exchanger with DX Coil Unit)
Control specifications
No.
Item
Specification outline
Remarks
1
When the
power is
reset
1) Judge the outdoor unit
The outdoor unit is judged when the power is reset. The control is switched
depending on the judgment result.
2) The check code is cleared when the power is reset during the occurrence of an
error. If an abnormal state continues even after the unit is restarted by pressing the
[ON / OFF] button on the remote controller, the check code is redisplayed on the
remote controller.
2
Single
operation
1) Pressing the [VENT.] button allows you to operate only the Air to Air Heat
Exchanger with DX Coil Unit in the remote control group by setting CODE [31]
Single operation of ventilation of the header unit to "1: Possible" when the Air to Air
Heat Exchanger with DX Coil Unit is connected to the remote control group with the
normal indoor unit set as the header unit (when in air-conditioning linkage system).
* The operation mode is always "fan" in Air to Air Heat Exchanger with DX Coil Unit-
only operation. The external input / output signals differ from those of the normal
operation. When using the external signals, use the terminal of the header unit
(normal indoor unit).
CODE No.
[31]
3
Operation
switch
1) The operation is switched by the request from the remote controller.
* The AUTO mode cannot be selected for the Air to Air Heat Exchanger with DX
Coil Unit.
2) When CODE [31] Single operation of ventilation is set to "1: Possible" in air-
conditioning linkage system, the Air to Air Heat Exchanger with DX Coil Unit-only
operation is "fan" and the operation mode cannot be switched.
4
Ventilation
mode switch
1) The ventilation mode is switched by the request from the remote controller.
* The Bypass mode cannot be selected for the Air to Air Heat Exchanger with DX
Coil Unit.
CODE No.
[EA]
TRA: Return Air
Temperature
TOA: Outdoor Air
Temperature
Before operation
After operation
Operation status
Normal indoor unit : Operation continued
Air to Air Heat Exchanger with DX Coil Unit : Stopped
Stoppage status
Normal indoor unit : Stopped
Air to Air Heat Exchanger with DX Coil Unit : Fan
operation (*)
By remote controller
Description
Stop
Stop the air conditioner running
Fan
Fan operation
Cool
Cooling
Dry
Drying
Heat
Heating
By remote controller
After operation
Heat exchange
Always perform heat exchange.
Automatic
Heat exchange or Bypass
• Automatically select the operation mode and the
ventilation mode depending on TRA and TOA.
For details, see 12.