18
5
Refrigerating cycle diagram
Indoor unit
Component
Description
Pulse modulating
valve
PMV
(Connector CN82 (6P): Blue)
1.Super heat control function in cooling
2.Under cool control function in heating
3.Cool refrigerant oil collection function
4.Heat refrigerant oil collection function
Temperature
sensor
1. TC1
(Connector CN100 (3P): Brown)
1.For Super heat control in cooling
2. TC2
(Connector CN101 (2P): Black)
1.For Under cool control in heating
3. TCJ
(Connector CN102 (2P): Red)
1.For Super heat control in cooling
4. TFA
(Connector CN103 (2P): Green)
1.For discharge temperature detection
5. TSA
(Connector CN104 (2P): Yellow)
1.For detecting Air Suction Temperature of direct expansion coil
Liquid
side
Gas
side
Strainer
Pulse
modulating
valve
Capillary
Strainer
Sensor
(TC2)
Sensor
(TCJ)
Sensor
(TFA)
Indoor Heat Exchanger
(Expansion coil)
Fan
Sensor (TSA)
Fan motor
M