103
(4)Outdoor cycle data display (Displayed on the center unit)
* Used to display the terminal unit information on the 7-segment display of the center unit.
Note:
The terminal unit is set by SW03 switch.
SW01 SW02 SW03
Description
3
1
1 to 3
Error data
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B Displays the check code (Only the latest one)
When there is no check codee: [– – –]
2
–
A –
B –
3
Horse power of outdoor unit
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B 8 Horse power: [… … 8], 10 Horse power: [… 1 0], 12 Horse power: [… 1 2]
14 Horse power: [… 1 4], 16 Horse power: [… 1 6]
4
Compressor operation order
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B Displays the ON status of Compressor (x).
Displays " – " if Compressor (x) is not connected.
B
Compressor 1: ON
1 0 0
Compressor 2: ON
0 1 0
Compressor 3: ON
0 0 1
5
Fan mode
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B When stopped: [F … 0], Mode 63: [F 6 3]
6
Release signal
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B Normally: [r … …], When release signal is received: [r … 1]
7
Oil judgment
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B Normally: [… … …], When short: [… … L]
8
Current of compressor 1 operation
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B [
.
]
: Displays the operation current value in decimal
9
Current of compressor 2 operation
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B [
.
]
: Displays the operation current value in decimal
10
Current of compressor 3 operation
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B [
.
]
: Displays the operation current value in decimal
11
Fan operation current
A [U.
]
: SW03 setting No. + 1 (Outdoor unit No. U2 to U4)
B [
.
]
: Displays the operation current value in decimal
SW03
7-segment display A
1
U2
2
U3
3
U4
Summary of Contents for MD-VNK802HEXE