9
Troubleshooting
9-1. Failure diagnosis
(1) Before diagnosing failure
(a) Model
All models of Modular Multi Type (SMMS-i)
All models of Air to Air Heat Exchanger with DX Coil Unit (MMD-VNK
✽✽✽
, MMD-VN
✽✽✽
)
(b) Necessary tools / measuring instruments
• Phillips-head driver, flat-head driver, spanner, pliers, nipper, thumbtack for reset switch, etc.
• Tester, thermometer, pressure gauge, etc.
(c) Check the following before diagnosing. (The following phenomena are not malfunctions.)
(2) Procedure
If a malfunction has occurred, follow the procedure below:
NOTE
If the malfunction has been caused by the power failure other than the following check items or micro controller
malfunction due to noises, the diagnosis may be wrong. If there is a noise source, shield the remote controller wires
and signal wires.
No.
Symptom
Check
1
The compressor does not
run.
• During 3-minute delay (within 3 minutes after the compressor is turned
off)?
• Is the thermo off?
• During fan or timer operation?
• During initial communication of the system?
• In Bypass mode?
2
The indoor fan does not run. • Is the indoor / outdoor temperature out of range?
• During forced fan OFF control?
3
The outdoor fan does not
run, or the air speed
changes.
• During COOL low temperature operation control?
• During defrosting?
4
The indoor fan does not stop
running.
During overheat elimination control when heating is stopped?
5
The ON / OFF button on the
remote control does not
work.
During external remote control?
Failure
Check the check code on the
interface board of the center unit
Check the check code on the
interface board of the target terminal
Error
"E28"
Check the locations
and components
Other errors