204
Notes on the setting items (Code list : Example)
*1 On the PC board for service, the capacity in Code "11" is set to "0000 : Invalid".
When replacing the PC board, change the value to that of the target indoor unit.
Model
Code : 10
Capacity of the Air to Air Heat Exchanger with
DX Coil Unit
Code : 11
* Factory setting of EEPROM stored on the PC board for service
Whether there is a humidifier
Code : 40
* Factory setting of EEPROM stored on the PC board for service
DN
Item
Memo
Factory setting
01
Filter sign lighting time
0002 : 2500 H
02
Filter clogging
0000 : Normal
03
Central address
0099 : Unfixed
04
Specific indoor unit priority
0000 : No priority
06
Heat intake temperature shift
0002 : +2 °C
0F
Cold only
0000 : Heat pump
10
Model code
0050 : Air to Air Heat Exchanger with
DX Coil Unit
(Ceiling-embedded duct)
11
Capacity code
0000 : Invalid (*1)
12
Line address
0099 : Unfixed
13
Indoor unit address
0099 : Unfixed
14
Group address
0099 : Unfixed
28
Auto recovery from blackout
0000 : None
2A
Option / Abnormal input (CN70) switch
0002 : Humidifier input
2E
HA terminal (T10) switch
0000 : Normal (HA terminal)
32
Sensor switch
0000 : Body sensor
40
Humidifier type setting
0000 : No humidifier
47
Ventilation fan speed during nighttime heat purge
operation
0000 : Low fixed
48
Unbalanced fan speed ventilation
0000 : Invalid
4C
Nighttime heat purge setting
0000 : Invalid
4E
Linkage with external devices
0000 : ON / OFF linked
5C
Damper output
0000 : Normal
60
Timer setting (wired remote controller)
0000 : Possible
BB
Humidity judgment by outdoor temperature
0000 : Not judged
BD
Continuous humidifying time
0006 : 6 hours
BE
Delay after drainage
0015 : 15 minutes
C9
Air to Air intake temperature correction (Cool)
0004 : –2.0 °C
CA
Air to Air intake temperature correction (Heat)
0005 : 2.5 °C
D0
Power saving mode
0001 : Valid
EA
Current ventilation mode
0002 : Automatic mode
EB
Current ventilation fan speed
0002 : High
ED
Operation output
0000 : Normal operation only
EE
Abnormal signal / Bypass mode signal switch
0000 : Abnormal signal output
SET DATA
Model
Model name (abbreviation)
0050
Air to Air Heat Exchanger with DX Coil Unit
(Ceiling-embedded duct)
MMD-VN(K)
✽✽✽
HEXE
SET DATA
Type
0000*
Invalid
0003
500 m
3
/h type
0007
800 m
3
/h type
0009
950 m
3
/h type
SET DATA
Type
0000*
No (MMD-VN
✽✽✽
HEXE)
0001
Yes (MMD-VNK
✽✽✽
HEXE)