363
6
F
2
S
0
8
3
4
Default setting (1A rating / 5A rating)
1CB-ARC
1CB-ARC
2CB-ARC
User
2TERM
3TERM
2TERM
3TERM
2TERM
3TERM
Setting
5A rating
1A rating
214
216
224
226
211
221
311
321
323
213
OST
OSTR1
3.0 - 30.0
15 - 150
Ω
Out of step relay
5.1 / 25
5.1 / 25
214
OSTR2
1.0 - 10.0
5 - 50
Ω
ditto
2.5 / 12
2.5 / 12
215
OSTXF
1.0 - 50.0
5 - 250
Ω
ditto
6.0 / 30
6.0 / 30
216
OSTXB
0.2 - 10.0
1 - 50
Ω
ditto
1.0 / 5
1.0 / 5
217
TOST1
0.01 - 1.00
s
ditto
0.04
0.04
218
TOST2
0.01 - 1.00
s
ditto
0.04
0.04
219
OCH
2.0 - 15.0
0.4 - 3.0
A
Overcurrent element
6.0 / 1.2
6.0 / 1.2
220
TSOTF
s
CB open detect timer for SOTF
5
5
221
CBF
OCBF
0.5 - 10.0
0.1 - 2.0
A
Overcurrent element
4.0 / 0.8
4.0 / 0.8
222
TBF1
50 - 500
ms
CBF timer for re-trip
150
150
223
TBF2
50 - 500
ms
CBF timer for related trip
200
200
224
OCD
0.5 (fixed)
0.1 (fixed)
A
Curr. change detector
--
--
225
OCCR
0.4 (fixed)
0.08 (fixed)
A
OC element
--
--
226
DEF
DEFFI
0.5 - 5.0
0.10 - 1.00
A
Directional earth fault element
1.0 / 0.20
1.0 / 0.20
227
DEFFV
1.7 - 21.0
V
ditto
2.0
2.0
228
DEFRI
0.5 - 5.0
0.10 - 1.00
A
ditto
1.0 / 0.20
1.0 / 0.20
229
DEFRV
1.7 - 21.0
V
ditto
2.0
2.0
230
DEF
θ
0 - 90
deg
ditto
85
85
231
DEF
TDEF
0.00 - 10.00
s
Forward definte timer
3.00
3.00
232 BU-trip
TDER
0.00 - 10.00
s
Reverse definite timer
3.00
3.00
233
OC
OC
0.5 - 100.0
0.1 - 20.0
A
OC element
6.0 / 1.2
6.0 / 1.2
234
TOC
0.00 - 10.00
s
ditto
3.00
3.00
235
OCI
OCI
0.5 - 25.0
0.10 - 5.00
A
IDMT OC element
1.0 / 0.20
1.0 / 0.20
236
TOCI
0.05 - 1.00
-
ditto
0.50
0.50
237
TOCIR
0.0 - 10.0
s
OC definite time reset delay
0.0
0.0
238
EF
EF
0.5 - 5.0
0.10 - 1.00
A
Earth fault OC element
1.0 / 0.20
1.0 / 0.20
239
TEF
0.00 - 10.00
s
ditto
3.00
3.00
240
EFI
EFI
0.5 - 5.0
0.10 - 1.00
A
IDMT earth fault OC element
1.0 / 0.20
1.0 / 0.20
241
TEFI
0.05 - 1.00
-
ditto
0.50
0.50
242
TEFIR
0.0 - 10.0
s
EF definite time reset delay
0.0
0.0
243
EFL
0.5 - 5.0
0.10 - 1.00
A
EF element for ZG fail safe
1.0 / 0.20
1.0 / 0.20
244
UVC
UVCV
10 - 60
V
Undervoltage element with current
compensation
48
48
245
UVCZ
0.0 - 50.0
0.0 - 250.0
Ω
ditto
2.0 / 10.0
2.0 / 10.0
246
UVC
θ
45 - 90
deg
ditto
85
85
247
UVCKrs
0 - 1000
%
ditto
-- (Linked with Krs of ZG)
-- (Linked with Krs of ZG)
248
UVCKxs
0 - 1000
%
ditto
-- (Linked with Kxs of ZG)
-- (Linked with Kxs of ZG)
249
OVG
20 (fixed)
V
OV element
--
--
250
UVFS
50 - 100
V
UV ph-ph element
88
88
251
UVLS
50 - 100
V
UV ph-ph element "L" level
77
77
252
UVFG
10 - 60
V
UV ph-g element
51
51
253
UVLG
10 - 60
V
UV ph-g element "L" level
45
45
254
UVPWI
30 (fixed)
V
UV for positive weak infeed
--
--
255
OCDP
0.5 - 10.0
0.1 - 2.0
A
Curr. change detector for fault under PSB
4.0 / 0.8
4.0 / 0.8
256
OVS
OVS1
5.0 - 150.0
V
OVS1 element
120.0
120.0
257
TOS1I
0.05 - 100.00
-
OVS1 IDMT timer
10.00
10.00
258
TOS1
0.00 - 300.00
s
OVS1 definite timer
0.10
0.10
259
TOS1R
0.0 - 300.0
s
OVS1 definite time reset delay
0.0
0.0
260
OS1DP
10 - 98
%
OVS1 DO/PU ratio
95
95
261
OVS2
5.0 - 150.0
V
OVS2 element
140.0
140.0
262
TOS2
0.00 - 300.00
s
OVS2 definite timer
0.10
0.10
263
OS2DP
10 - 98
%
OVS2 DO/PU ratio
95
95
264
OVG
OVG1
5.0 - 150.0
V
OVG1 element
70.0
70.0
265
TOG1I
0.05 - 100.00
-
OVG1 IDMT timer
10.00
10.00
266
TOG1
0.00 - 300.00
s
OVG1 definite timer
0.10
0.10
267
TOG1R
0.0 - 300.0
s
OVG1 definite time reset delay
0.0
0.0
268
OG1DP
10 - 98
%
OVG1 DO/PU ratio
95
95
269
OVG2
5.0 - 150.0
V
OVG2 element
80.0
80.0
270
TOG2
0.00 - 300.00
s
OVG2 definite timer
0.10
0.10
271
OG2DP
10 - 98
%
OVG2 DO/PU ratio
95
95
272
UVS
UVS1
5.0 - 150.0
V
UVS1 element
60.0
60.0
273
TUS1I
0.05 - 100.00
-
UVS1 IDMT timer
10.00
10.00
274
TUS1
0.00 - 300.00
s
UVS1 definite timer
0.10
0.10
275
TUS1R
0.0 - 300.0
s
UVS1 definite time reset delay
0.0
0.0
276
UVS2
5.0 - 150.0
V
UVS2 element
40.0
40.0
277
TUS2
0.00 - 300.00
s
UVS2 definite timer
0.10
0.10
278
VSBLK
5.0 - 20.0
V
UVS blocking threshold
10.0
10.0
279
UVG
UVG1
5.0 - 150.0
V
UVG1 element
35.0
35.0
280
TUG1I
0.05 - 100.00
-
UVG1 IDMT timer
10.00
10.00
281
TUG1
0.00 - 300.00
s
UVG1 definite timer
0.10
0.10
282
TUG1R
0.0 - 300.0
s
UVG1 definite time reset delay
0.0
0.0
Units
Contents
№
0 - 300
Name
Range
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...