3.5 Metering
Function
The GRZ100 performs continuous measurement of the analog input quantities. The currents and
voltages at remote terminals can be also displayed. The measurement data shown below is updated
every second and displayed on the LCD of the relay front panel or on the local or remote PC.
[Local terminal]
-
Magnitude and phase angle of phase voltage (Va, Vb, Vc)
-
Magnitude and phase angle of phase-to-phase voltage (Vab, Vbc, Vca)
-
Magnitude and phase angle of symmetrical component voltage (V1, V2, V0)
-
Magnitude and phase angle of phase voltage for autoreclose (Vs1, Vs2)
-
Magnitude and phase angle of phase current (Ia, Ib, Ic)
-
Magnitude and phase angle of phase-to-phase current (Iab, Ibc, Ica)
-
Magnitude and phase angle of symmetrical component current (I1, I2, I0)
-
Magnitude of parallel line zero sequence current (I0m)
-
Percentage of thermal capacity (THM%)
-
Active power and reactive power (P, Q)
- Frequency
-
Telecommunication delay time 1 at the remote terminal 1
-
Telecommunication delay time 2 at the remote terminal 2
[Remote terminal 1]
-
Magnitude and phase angle of phase voltage (Va1, Vb1, Vc1)
-
Magnitude and phase angle of phase-to-phase voltage (Vab1, Vbc1, Vca1)
-
Magnitude and phase angle of symmetrical component voltage (V11, V21, V01)
-
Magnitude and phase angle of phase current (Ia1, Ib1, Ic1)
-
Magnitude and phase angle of phase-to-phase current (Iab1, Ibc1, Ica1)
-
Magnitude and phase angle of symmetrical component current (I11, I21, I01)
[Remote terminal 2]
-
Magnitude and phase angle of phase voltage (Va2, Vb2, Vc2)
-
Magnitude and phase angle of phase-to-phase voltage (Vab2, Vbc2, Vca2)
-
Magnitude and phase angle of symmetrical component voltage (V12, V22, V02)
-
Magnitude and phase angle of phase current (Ia2, Ib2, Ic2)
-
Magnitude and phase angle of phase-to-phase current (Iab2, Ibc2, Ica2)
-
Magnitude and phase angle of symmetrical component current (I12, I22, I02)
Phase angles above are expressed taking the positive sequence voltage as a reference phase angle,
where leading phase angles are expressed as positive, (+).
The above system quantities are displayed in values on the primary side or on the secondary side
determined by the setting. To display accurate values, it is necessary to set the CT ratio and VT
ratio as well. For the setting method, see "Setting the line parameters" in 4.2.6.7.
The signing of active and reactive power flow direction can be set positive for either power
sending or power receiving. The signing of reactive power can be also set positive for either
lagging phase or leading phase. For the setting method, see 4.2.6.6.
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...