33
6
F
2
S
0
8
3
4
Element Range
Step
Default
Remarks
ZNDG
0.01 - 100.00
Ω
0.01
Ω
10.00
Ω
ZND reach
(0.1 – 500.0
Ω
0.1
Ω
50.0
Ω
)
BNDG
0.10 - 20.00
Ω
0.01
Ω
12.00
Ω
ZNDG blinder reach
(0.5 - 100.0
Ω
0.1
Ω
60.0
Ω
)
Krs
0 - 1000 %
1%
340%
Residual current compensation = R0/R1
Kxs
0 - 1000 %
1%
340%
Residual current compensation = X0/X1
Krm
0 - 1000 %
1%
300%
Mutual coupling compensation = ROM/R1
Kxm
0 - 1000 %
1%
300%
Mutual coupling compensation = XOM/X1
KrsR
0 - 1000 %
1%
100%
Residual current compensation for ZR = R0/R1
KxsR
0 - 1000 %
1%
100%
Residual current compensation for ZR = X0/X1
TZ1G
0.00 - 10.00 s
0.01 s
0.00 s
Zone 1 timer
TZ2G
0.00 - 10.00 s
0.01 s
0.30 s
Zone 2 timer
TZFG
0.00 - 10.00 s
0.01 s
0.35 s
Zone F timer
TZ3G
0.00 - 10.00 s
0.01 s
0.40 s
Zone 3 timer
TZR1G
0.00 - 10.00 s
0.01 s
0.50 s
Zone R1 timer
TZR2G
0.00 - 10.00 s
0.01 s
0.60 s
Zone R2 timer
TZNDG
0.00 - 10.00 s
0.01 s
0.70 s
Zone ND timer
UVC
Phase selection element
UVCV
10 - 60 V
1 V
48 V
Voltage setting
UVCZ
0.0 - 50.0
Ω
0.1
Ω
2.0
Ω
Reach setting
(0 - 250
Ω
1
Ω
10
Ω
)
UVC
θ
45° - 90°
1°
85°
Characteristic angle
EFL
0.5 – 5.0 A
0.1 A
1.0 A
Earth fault detection
(0.10 – 1.00 A
0.01 A
0.20 A)
UVPWI
30 V fixed
UV for positive weak infeed
Scheme switch
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP
/BOP/POP+DEF/UOP+DEF/
BOP+DEF/PUP+DEF
POP
Scheme
selection
CRSCM OFF/ON
ON Telecommunication
service
BLZONE
COM/IND
COM
Common or independent setting for blinder
Z1CNT
1/2/3/4/5
1
Zone 1 trip mode selection
PSB - Z1
OFF/ON
ON
Z1 power swing blocking
PSB - Z2
OFF/ON
ON
Z2 power swing blocking
PSB - Z3
OFF/ON
OFF
Z3 power swing blocking
PSB - ZF
OFF/ON
OFF
ZF power swing blocking
PSB - ZR1
OFF/ON
OFF
ZR1 power swing blocking
PSB - ZR2
OFF/ON
OFF
ZR2 power swing blocking
ZFBT
OFF/ON
OFF
ZF backup tripping
ZR1BT
OFF/ON
OFF
ZR1 backup tripping
ZR2BT
OFF/ON
OFF
ZR2 backup tripping
ZNDBT
OFF/ON
OFF
ND zone backup tripping
UVPWIEN
OFF/ON
OFF
Countermeasures for overreaching of a
leading-phase distance element at positive
phase weak infeed condition
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the case
of 5 A rating.
(*2) Valid only when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid only when quadrilateral characteristic is selected by ZS-C and ZG-C.
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...