Connect a phase angle meter to the three-phase voltages taking the scheme switch [VT-RATE]
and [VTPHSEL] setting into consideration. The phase angle meter connection shown in Figure
6.5.1.7 is the case for the default settings, that is, [VT-RATE] and [VTPHSEL] are set to "PH/G"
and "A" respectively.
[VT-RATE] setting
[VTPH-SEL] setting
Meter connection phase
PH/G A
A-N
B B-N
C C-N
PH/PH A
A-B
B B-C
C C-A
Voltage check element OVB, UVB, OVL1, UVL1, OVL2, and UVL2
•
Press 5 (= Logic circuit) on the "Test" screen to display the Logic circuit screen.
•
Enter a signal number for TermA line to observe at monitoring jack A and press the ENTER
key.
•
Apply three-phase rated voltage and single-phase rated voltage as shown in Figure 6.5.1.7.
OVB and UVB:
•
Change the magnitude of the three-phase voltage if the scheme switch [3PH-VT] is set to
"Bus" or adjust the magnitude of the single-phase voltage if it is set to "Line". Measure the
value at which the element operates and check that it is within
±
5% of the setting.
OVL1 and UVL1:
•
Adjust the magnitude of the single-phase voltage if the scheme switch [3PH-VT] is set to
"Bus"; adjust the magnitude of the three-phase voltage if the scheme switch [3PH-VT] is set to
"Line". Measure the value at which the element operates and check that it is within
±
5% of the
setting.
OVL2 and UVL2:
•
Adjust the magnitude of voltage applied to terminal 17 and 18 and measure the value at which
the element operates. Check that the measured value is within
±
5% of the setting.
Synchronism check element SYN1
•
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
•
Enter a signal number for TermA line to observe at monitoring jack A and press the ENTER
key.
•
Apply a three-phase rated voltage and a single-phase rated voltage as shown Figure 6.5.1.7.
Voltage check:
•
Set the three-phase voltage to any value over the SY1OV setting. (The default setting of
SY1OV is 51 V.)
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...