220
6
F
2
S
0
8
3
4
•
Enter the numerical value and press the ENTER key for each element.
•
After setting all elements, press the END key to return to the "Protection element" menu.
<PSB&OST>
•
Press 2 (= PSB&OST) to display the "PSB & OST" screen. The measuring elements and
timers used in the power swing blocking and out-of-step tripping are set using this screen.
/7 PSB&OST 1/ 9
PSBSZ( 0.50- 15.00): 0.50 _ Ω
PSBGZ( 0.50- 15.00): 0.50 _ Ω
TPSB ( 20- 60): 40 ms
OSTR1( 3.0- 30.0): 1.0 Ω
OSTR2( 1.0- 10.0): 1.0 Ω
OSTXF( 1.0- 50.0): 1.0 Ω
OSTXB( 0.2- 10.0): 0.2 Ω
TOST1( 0.01- 1.00): 0.01 s
TOST2( 0.01- 1.00): 0.01 s
•
Enter the numerical value and press the ENTER key for each element.
•
After setting all elements, press the END key to return to the "Protection element" menu.
<OC, DEF&UV>
•
Press 3 (= OC, DEF&UV) to display the "OC, DEF&UV" screen. The overcurrent,
undervoltage and directional earth fault elements and timers are set using this screen.
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...