If OAT is invalid (not transmitted by the Inverter, out of range value, etc.), the Water Setpoint is equal to the
current Max. Water Temp.
•
If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the current Min. Water
Temp.
•
The climatic curve corresponds corresponds to the water setpoint in Home mode. To define the other
occupancy modes, it is necessary to configure Heating Sleep Offset [P402] and Heating Away Offset
[P403]:
10.3.2
Fixed water setpoint:
If the cooling climatic curve [P586] or the heating climatic curve [P581] is configured to “-1”, the water control point
will be determined according to the Occupancy mode.
The water setpoint can be configured in two ways:
-- By direct access to the RC (refer to owner’s manual)
-- By accessing the parameter menu via RC or JBus / ModBus
COOLING:
RC Occupancy
Water setpoint on
RC direct access
Range
Water setpoint on
parameter menu
Range
Cool Home Setpoint
5 to 18°C
Cool Home Setpoint [P407]
5 to 18°C
Cool Sleep Setpoint
5 to 18°C
Cool Home Setpoint [P407] +
Cool Sleep Offset [P408]
0 to 10°C
Cool Away Setpoint
5 to 18°C
Cool Home Setpoint [P407] +
Cool Away Offset [P409]
0 to 10°C
HEATING:
RC Occupancy
Water setpoint on
RC direct access
Range
Water setpoint on parameter
menu
Range
Heat Home Setpoint
20 to 60°C
Heat Home Setpoint [P401]
20 to 60
Heat Sleep Setpoint
20 to 60°C
Heat Home Setpoint [P401] +
Heat Sleep Offset [P402]
-10 to 0°C
Heat Away Setpoint
20 to 60°C
Heat Home Setpoint [P401] +
Heat Away Offset [P403]
-10 to 0°C
OAT (°C)
W
ater Setpoint (
°C
)
Heating Climatic Curves (K7 to K8)
Example:
OAT (°C)
W
ater Setpoint (
°C
)
Heating Climatic Curves in function of occupancy mode
Home
Sleep
Away