Monobloc Outdoor Unit Installation Manual
9.3.3 Parameter configuration
No.
Step
Parameter Description
Para No.
Range
Default
Example Set Up
1
DHW Mode
Config.
Refer to “Installation with DHW Production” for DHW set-up
2
Boiler Config.
Back up type:
Selects the type of boiler used on installation:
0 = No backup
9 = Backup by Oil or Gas boiler
1 to 8 = not used for this configuration
601
0 ~ 9
0
9
Minimum OAT for heating:
The heat pump is not allowed to run in heating mode if the OAT drops
below this threshold temperature (°C)
514
-20 ~ 10
-20
-7
3
Additional
Pump Config.
Additional pump logic:
This Parameter defines the function of an additional pump, in standby
mode, if no user interface or local user interface is connected
0 = No additional pump
1 = Always ON except in OFF mode
3 = Always ON except in OFF mode or when DHW mode is active
2 & 4 = not used in this configuration
573
0 ~ 4
0
See pump
configuration
(section 10.8)
Additional pump logic:
This Parameter defines the function of an additional pump, in standby
mode, if a remote user interface is connected
0 = No additional pump
1 = According to space temperature: pump OFF except when there is
a demand from the room temperature
4 = Pump OFF except when there is a demand from the room
temperature and no DHW is active
1 & 3 = not used in this configuration
0 ~ 4
0
See pump
configuration
(section 10.8)