Monobloc Outdoor Unit Installation Manual
•
If OAT is invalid, the Water Setpoint is equal to the Custom Max. Water Temp [P585].
•
If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the Custom Min. Water
Temp [P584].
•
If Min. OAT is greater or equal to Max. OAT threshold, the Water Setpoint is equal to the Custom Max.
Water Temp [P584].
10.3.4
Offset on climatic curves (predefined and customer)
Two other parameters are also configurable to adjust water setpoint to suit customer needs:
• For cooling curve - Cool Minimum Water Setpoint [P589]can be offsetted by an offset on foot of the curve
(Cool Curve Min Stp Offset [P413])
• For heating curve - Heat Maximum Water Setpoint [P585] can be offsetted by an offset on head of the
curve (Heat Curv Max Stp Offset [P412])
W
ater Setpoint (
°C
)
OAT (°C)
Custom Cooling Climatic Curve: offset on foot of the curve
W
ater Setpoint (
°C
)
OAT (°C)
Heating Climatic Curve: offset on head of the curve