67
Monobloc Outdoor Unit Installation Manual
DHW only (setpoints defined below change also the setpoints for DHW mode):
RC Occupancy
Water setpoint on
RC direct access
Range
Water setpoint on
parameter menu
Range
DHW Setpoint
30 to 60°C
DHW Setpoint [P406]
30 to 60°C
DHW Anti Legionella
Setpoint
50 to 60°C
DHW Anti-Legionella
Stp [P405]
50 to 60°C
10.3.3
Custom climatic curve:
COOLING:
If the cooling climatic curve [P586] is configured to “0”, the water setpoint will be calculated according
to the custom cooling climatic curve.This custom cooling climatic curve can be defined using the following
parameters:
Parameter
Description
Default
Min.
Max.
P587
Custom Minimum OAT
20°C
0°C
30°C
P588
Custom Maximum OAT
35°C
24°C
46°C
P589
Custom Minimum Water Temp
10°C
5°C
18°C
P590
Custom Maximum Water Temp
18°C
5°C
18°C
•
If OAT is invalid, the Water Setpoint is equal to the Custom Minimum Water Temp [P589].
•
If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the Custom Maximum
Water Temp [P590].
•
If Minimum OAT is greater or equal to Maximum OAT threshold, the Water Setpoint is equal to the Custom
Maximum Water Temp [P590].
HEATING:
If the heating climatic curve [P581]is configured to “0”, the water setpoint will be calculated according
to the custom heating climatic curve. This custom heating climatic curve can be defined using the following
parameters:
Parameter
Description
Default
Min.
Max.
P582
Custom Minimum OAT
-7°C
-30°C
10°C
P583
Custom Maximum OAT
20°C
10°C
30°C
P584
Custom Minimum Water Temp
20°C
20°C
40°C
P585
Custom Maximum Water Temp
38°C
30°C
60°C
Example:
OAT (°C)
Custom Heating Climatic Curve
WSP
(°C
)
Default
min
max
Default
min
max
Example:
OAT (°C)
Custom Cooling Climatic Curve
WSP
(°C
)