91
Monobloc Outdoor Unit Installation Manual
Check Code
Diagnostic functional operation
Determination and action
Alarm [P344]
Curr
ent Alarm [P346] to [P349]
Past Alarm [P350] to [P354]
Operational Cause
Unit Status
Automatic
Reset
227
74
Discharge temperature too high
Compressor stop
O
Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error
becomes definite after retrying operation for 4 times.
1. Check refrigerant circuit (Gas leak).
2. Check electronic expansion valve.
3. Check discharge temp. sensor (TD).
229
75
Missing phase in power cable
Compressor stop
O
Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error
becomes definite after retrying operation for 8 times.
1. Check power supply voltage.
231
76
Inverter heatsink temperature
too high
Compressor stop
O
Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error
becomes definite after retrying operation for 4 times.
1. Check heat sink airflow path.
-
80
Real time clock failure on NHC
board
Continue
X
-
81
EEPROM corrupted on NHC
board
Continue
O
127
82
Inverter EEPROM not readable of
EEPROM number out of range
Stop
O
Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error caused
by delay of communication
-
90
Invalid configuration
Stop
X
Automatic reset when configuration is correct
-
100
Emergency stop
Stop
X
Automatic reset when [P055] is reset
-
200
External alarm
Continue
X
Automatic reset when contact is closed