Monobloc Outdoor Unit Installation Manual
7.8.2 Control Line Connection
7.8.3 Electrical supply / cable specifications
Cable specifications (power)
The power supply must conform to the specification on the Monobloc outdoor unit nameplate. The supply voltage
must be within the range specified in the electrical data table shown below:
Model Name
(RUA)
Power Supply
1
Maximum
Current (A)
Installation
Fuse Rating
(A)
2
Power Wire
(mm
2
)
3
Connection
Destination
CP1701H*
360-440V 3N~ 50Hz
18.5
25
4
TB X1
L1, L2, L3, N
CP2101H*
360-440V 3N~ 50Hz
21.2
25
4
Note:
1 Nominal power supply = 400V 3N~ 50Hz
2 When using a circuit breaker use 25A Type C
When using fuses use 25A Type gG
3 Use H07RNF cable to connect the power supply to the Monobloc outdoor unit.
Maximum permissible cable = 5G6mm
2
The maximum cable length will be determined by the installation method (free air, conduit etc.) and the volt
drop for the circuit (maximum permissible volt drop ≤5%)
Water or Air
temperature
control
Ext. Circulator
(on/off)
Normal/Alarm
Normal/Defrost
Boiler or
Electric Heater (up to 3 stages)
Domestic Hot
Water Valve
(On/Off)
Domestic Hot Water
Backup Electric Heater
(1 stage)
Power
(3Ph. + N)
Option / Accessory
Estia Domestic hot
water Tank
OR
Customer supplied
DHW Tank &
Domestic hot water
Tank Temperature
sensor
Outdoor Air Temp (OAT) C
°
Safety Switch
Domestic Hot water (DHW) C
°
4 Customized inputs
Power limitation switch
Off peak sitch
Loadshed request switch
Solar input switch
DHW request switch from tank
DHW priority switch
Anti-legionella cycle request
switch
Safety switch