58
Monobloc Outdoor Unit Installation Manual
No.
Step
Figure
FC
Designation
Description
Range
Default
Ex.
5
Configure Follower 1
Apply procedure “Manage the Header and Follower units with a common user interface” to pass on
Follower 1 status
742 Header / Follower
selection
Allow the Header/Follower
operation as Follower:
0 = Disable
1 = Header
2 = Follower
0 ~ 2
0
2
521
User interface
type
Configure User interface for
Follower:
0 = No User Interface
1 = Remote control by contacts
or SUI
2 = RC remotely installed in the
house (Air setpoint)
3 = RC remotely installed in the
house (Water setpoint)
0 ~ 3
0
1
6
Configure Follower 2
Apply procedure “Manage the Header and Follower units with a common user interface” to pass on
Follower 2 status
742 Header / Follower
selection
Allow the Header/Follower
operation as Follower:
0 = Disable
1 = Header
2 = Follower
0 ~ 2
0
2
521
User interface
type
Configure User interface for
Follower:
0 = No User Interface
1 = Remote control by contacts
or SUI
2 = RC remotely installed in the
house (Air setpoint)
3 = RC remotely installed in the
house (Water setpoint)
0 ~ 3
0
1
7
Main V
ariable speed pump configuration for Header/
Follower installation
If the units are fitted with internal main variable speed pump, then several parameters are to set for each unit of Header / Follower
installation
To configure main pump of Header unit, the other units of installation must be in mode OFF
(only Header unit is activated)
Apply procedure “Manage the Header and Follower units with a common user interface” to pass on
Header status
758 Header / Follower
pump type
0 = No pump control
1 = Common Water Pump (a
pump is installed outside of the
unit on the water loop and is
controlled by the Header unit)
2 = Individual Water Pump:
running according to
H/F Overall Status (P229)
3 = Individual Water Pump:
stopped if unit is satisfied
0 ~ 3
2
2
Determine the minimum pump speed and adjust the pump speed to obtain the expected water flow
rate to allow closure of flow switch (see section 11.4) – Line “variable speed pump – control on
adjustable constant speed