10.9 Electric Heaters:
NOTE:
The installer is responsible for ensuring that the installation complies with the applicable legislation in
terms of electrical and thermal safety.
It is possible to include electric heaters in the hydraulic circuit to ensure heating in case of low OATor heat pump
failure.
When the OAT is below the Booster OAT Threshold [P604], then the booster electric heaters can be activated.
The booster electric heaters can operate at the same time as the heat pump.
When OAT is below Min OAT for heating [P514], the heat pump is stopped, and the electric heaters can be
activated.
Operation of booster and backup:
Depending on the configuration, it is possible to control up to three electric heaters or three electric heat stages
(see section 7.8.12):
•
One electric heat stage with one customized discrete output: EH1.
•
Two electric heat stages with two customized discrete outputs: EH1 and EH2.
•
Three electric heat stages with two customized discrete outputs: EH1 and EH2.
•
Three electric heat stages with three customized discrete outputs: EH1 and EH2 and EH3. This configuration
cannot be activated if DHW heater is present.
Each discrete output can control a contactor (not supplied with unit).
Characteristics
Contactor Coil:
230 VAC
50Hz
Electrical connection
Refer to Installation with booster electric heaters example
Configuration
Refer to Installation with booster electric heaters example
10.10 Boiler:
To satisfy the heating demand during periods very low ambient temperature, it is possible to install a boiler. The
boiler is considered as a backup: when it is activated, the heat pump cannot operate. Boiler is activated when OAT
is below Minimum OAT for Heating [P514] or in case of heat pump failure.
Characteristics
Contactor Coil:
230 VAC
50Hz
Electrical connection
Refer to Installation with DHW and boiler example
Configuration
Refer to Installation with DHW and boiler example
Heating needs
Capacity of heat pump
OAT
Min OAT for heating (P514)
Booster OAT Threshold (P604)
Boiler only or
backup heaters
Electric
heat pumps
Heat pump only