46
Monobloc Outdoor Unit Installation Manual
8.3 JBus Register Addresses
Par.
JBus Addr
Mnemonic
Description
Range
Unit
RC
JBus
001
0001H
OAT
Outdoor Air Temperature
-
1/10°C
RO/d
RO/F
002
0002H
IAT
Indoor Air Temperature
-
1/10°C
RO/d
RO/F
003
0003H
EWT
Entering Water Temperature
-
1/10°C
RO
RO/F
004
0004H
LWT
Leaving Water Temperature
-
1/10°C
RO
RO/F
005
0005H
TR
Refrigerant Temperature
-
1/10°C
RO
RO/F
006
0006H
SPARE_T
Spare Temperature
-
1/10°C
RO
RO/F
008
0008H
sst
Saturated Suction Temp
-
1/10°C
RO
RO
009
0009H
ts
Suction Temperature
-
1/10°C
RO
RO
010
000AH
td
Discharge Temperature
-
1/10°C
RO
RO
011
000BH
te
Lower Air Exchanger Temp
-
1/10°C
RO
RO
012
000CH
tl
Upper Air Exchanger Temp
-
1/10°C
RO
RO
013
000DH
to
Inv. Outdoor Air Temp
-
1/10°C
RO
RO
014
000EH
th
Heatsink Temperature
-
1/10°C
RO
RO
015
000FH
sh
Superheat Temperature
-
1/10 K
RO
RO
016
0010H
sh_targ
Superheat Target Temp
-
1/10 K
RO
RO
017
0011H
dc_volt
Inverter DC High Voltage
-
V
RO
RO
018
0012H
hv_stat
HV Bus Comm. Status
0/1 [Normal/Alarm]
-
RO
RO
019
0013H
inv_mod
Inverter Current Mode
-
-
RO
RO
020
0014H
freq_min
Actual Min Compr. Freq
-
1/10 Hz
RO
RO
021
0015H
freq_max
Actual Max Compr. Freq
-
1/10 Hz
RO
RO
022
0016H
FREQ_REQ
Requested Compr. Freq
-
1/10 Hz
RO
RO/F
023
0017H
freq_cur
Actual Compressor Freq
-
1/10 Hz
RO
RO
024
0018H
pmv_pos
PMV Position
0 to 500
step
RO
RO
027
001BH
upr_fan
Upper Fan Speed
0 to 1000
rpm
RO
RO
028
001CH
lwr_fan
Lower Fan Speed
0 to 1000
rpm
RO
RO
029
001DH
EXCH_HTR
Exchanger Heater
0/1 [Off/On]
-
RO
RO/F
030
001EH
BOILER
Boiler Output
0/1 [Off/On]
-
RO
RO/F
031
001FH
EHS
Electrical Heat Stages
0 to 3
-
RO
RO/F
041
0029H
CHIL_OCC
Occupancy Mode
0 to 2 [Away/Sleep/Home]
-
RW/d
RW/F
042
002AH
sum_mode
Summer Mode
0/1 [No/Yes]
-
RO
RO
043
002BH
nightmod
Night Mode
0/1 [No/Yes]
-
RO
RO
044
002CH
MOD_REQ
System Mode Request
0 to 9
-
RW/d
RW/F
045
002DH
MOD_STAT
System Mode Status
0 to 109
-
RO/d
RO
047
002FH
mod_ovr
System Mode Override
0 to xxx
-
RO
RO
048
0030H
setpoint
Current Setpoint
0.0 to 60.0
1/10°C
RW/d
RO
049
0031H
RESET
User Adjust Temperature
-5.0 to 5.0
1/10 K
RO
RO/F
051
0033H
CTRL_PNT
Control Point
0.0 to 60.0
1/10°C
RO/d
RO/F
052
0034H
CTRL_TMP
Control Temp
-40.0 to 115.0
1/10°C
RO/d
RO/F
061
003DH
cmp_req
Compressor Mode Request
-
-
RO
RO
063
003FH
cmp_stat
Compressor Mode Status
-
-
RO
RO
064
0040H
cap_ovr
Capacity Override
-
-
RO
RO
065
0041H
cap_tmr
Capacity Timer
-
s
RO
RO
066
0042H
CAP_T
Total Capacity
0 to 100
%
RO
RO/F
067
0043H
DEM_LIM
Demand Limit
0 to 100
%
RO
RO/F
068
0044H
FREQ_RED
Frequency Reduction Mode
0/1 [No/Yes]
-
RO
RO/F
069
0045H
RUNNING
Unit Running Status
0/1 [No/Yes]
-
RO
RO/F
081
0051H
pmp_ovr
Pump Override
-1 to 16
-
RO
RO
082
0052H
flow_err
Water Flow Failure
0/1 [Normal/Alarm]
-
RO
RO
083
0053H
dtstp
Current DeltaT Setpoint
-
°C
RO
RO
084
0054H
delta_t
Water Delta Temperature
-
1/10 K
RO
RO
085
0055H
PMP
Water Pump Speed
0 to 100
%
RO
RO/F
088
0058H
ADD_PMP
Additional Pump Output
0/1 [Off/On]
-
RO
RO/F
091
005BH
Backup_ovr
Backup Override
-1 to 100
-
RO
RO
092
005CH
back_flg
Backup Authorized flag
0 to 1
-
RO
RO
093
005DH
warmtime
Booster Warm Up timer
0 to 18
s
RO
RO
094
005EH
BACK_CAP
Backup Capacity
0 to 100
%
RO
RO/F
101
0065H
ONOFF_SW
On/Off Switch Status
0/1 [Open/Close]
-
RO
RO/F
102
0066H
HC_SW
Heat/Cool Switch Status
0/1 [Open/Close]
-
RO
RO/F
103
0067H
ECO_SW
Eco Switch Status
0/1 [Open/Close]
-
RO
RO/F
104
0068H
SAFE_SW
Safety Switch Status
0/1 [Open/Close]
-
RO
RO/F
105
0069H
FLOW_SW
Flow Switch Status
0/1 [Open/Close]
-
RO
RO/F
106
006AH
CUST_DI5
Customized DI#5 Status
0/1 [Open/Close]
-
RO
RO/F
107
006BH
CUST_DI6
Customized DI#6 Status
0/1 [Open/Close]
-
RO
RO/F
108
006CH
CUST_DI7
Customized DI#7 Status
0/1 [Open/Close]
-
RO
RO/F