39
(1) Start the setting file creation software. Select [New] - [Touch Screen Controller(CT128series)],
Input each item entered in the work of "” into the setting file creation software settings screen.
*When using centralized controllers in combination (up to 8 units)
When using centralized controllers in combination including the Unit within the same TCC-LINK, apply the following
settings.
When using multiple units of the Unit in combination (master/slave setting)
• The Unit - header unit (1 unit): No setting required
• The Unit - follower unit:
Set to follower unit setting using the setting file creation software.
When using in combination with the TouchScreenController (BMS-CT512*)
• TouchScreenController (BMS-CT512*): No setting required
• The Unit:
Set to follower unit setting using the setting file creation software.
Also, turn ON 1 of DS25 on the Communication settings screen of the
main unit.
When using in combination with SmartBMS manager with data analyzer and a SmartBMS manager
• SmartBMS manager with data analyzer: No setting required
• The Unit:
Set to follower unit setting using the setting file creation software.
3-3. Upload setting data
* If LAN connection is difficult after the installation work, please implement "3-3.Upload setting data" before
"3-8.Installation work". If LAN connection is easy after installation work, "3-8.Installation work" may be
implemented after '’3-3.Upload setting data".
(1) Confirm that the setting content matches the on-site system.
(2) Connect the PC with the setting file creation software and the TouchScreenController main
unit with a LAN cable.
(3) Confirm that the HOME screen displays after turning on the main unit (after about 4 minutes).
(4) Set the PC’s IP address to the same network as the TouchScreenController such as
192.168.2.80.
(5) Display "Upload setting" in [File] - [Upload] in the setting file creation software.
(6) Confirm that it is connected to the TouchScreenController with the [ping] button.
(7) Upload the setting file to the TouchScreenController with the "Upload" button.
When not using the template function of the setting file creation software
Summary of Contents for BMS-CT1280UL
Page 1: ...Touch Screen Controller Model name BMS CT1280UL No A10 1903 1 ...
Page 47: ...47 5 Tap 5 1 The configured content is confirmed 5 1 5 1 ...
Page 49: ...49 4 Tap 4 1 The configured content is confirmed 4 1 4 1 ...
Page 56: ...Installation Manual ...
Page 71: ...Network Configuration Guide ...
Page 72: ...English Touch Screen Controller Model name BMS CT1280UL Network Configuration Guide ...
Page 76: ...Owner s Manual ...
Page 167: ...Copyright 2019 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...