Tolomatic User Guide:
ICR Rod Style Integrated Control Actuator
4-1
Power Supply Recommendations
4
4.1 Regulated and Unregulated Power Supplies
Both unregulated and regulated power supplies can be used to power the ICR
actuator. Unregulated supplies can be a better choice depending on the application
as they have a larger output capacitance, which makes them better energy
absorption sources. They are a good choice for applications that require aggressive
acceleration as they can supply peak currents without faulting and will not trip
on high voltage. However, unregulated power supplies do not have over voltage
protection and care must be taken not to exceed the maximum voltage of the
actuator by using a shunt regulator, and proper fusing to prevent excessive loading
of the supply.
Regulated supplies can be used, but additional measures may need to be taken.
To prevent regenerative energy from reaching the supply, a blocking diode and
capacitor, appropriately sized for the application, should be installed. In addition,
a shunt regulator may be needed to dissipate excess energy. The shunt regulator
available from Tolomatic (see page 4-4) has the appropriate bus capacitance,
requiring only the use of a blocking diode.
The ICR SV1B Basic and SV1P Plus actuators are intended to run off of an isolated
DC power source. The power supply that is required will depend on the application.
A 48V supply will allow the actuator to operate at maximum speed. A 24V supply
will result in approximately half the rated velocity. Input current will depend on the
actuator power needed in the installation. If operating more than one actuator on
the same power supply, add the required power supply rating for each actuator.
4.1.1. Power Supply Sizing Guidelines
Use the following tables to help determine the proper power source voltage for an
application or call Tolomatic at 1-800-328-2174 or 763-478-8000 for assistance.
NOTe:
Green numbers indicate power supply required in Watts for the given speed
and thrust indicated at outside margins.
WARNING!
All installations should
provide a means for a
hardware emergency
stop that removes power
from the actuator in an
emergency condition.
The actuator emergency
stop function should
not be relied on when
safety is required. It
is recommended to
disconnect only the + bus
power and keep the power
ground line connected.
BN02 - 1:1 RATIO
(Required Power - Watts)
SP
eed
(in/sec)
THRUST (lbf)
20
40
60
80
100 120 140 150
2
26
47
70
95
123 154 186 204
51
4
36
66
98
132 169 208 249 271
102
6
48
86
127 170 216 263 313 339
152
8
61
109 158 210 264 319 377 406
203
10
77
133 191 251 313 376 441 475
254
12
94
159 226 294 363 434 506 543
305
14
113 187 262 338 415 493 572 612
356
16
134 217 300 383 468 552 638 681
406
18
157 248 339 430 522 613
457
20
182 281 380 479 577
508
22
209 316 423 528
559
24
237 353 467
610
89
178 267 356 445 534 623 667
SP
eed
(mm/sec)
THRUST (N)
BN05 - 1:1 RATIO
(Required Power - Watts)
SP
eed
(in/sec)
THRUST (lbf)
50
100 150 200 250 300 350 400
1
51
66
89
118 155 199 251 309
25
2
64
91
124 164 212 265 326 394
51
3
78
116 160 210 266 329 398 473
76
4
94
142 196 255 320 390 465 546
102
5
111 170 233 300 372 448 528 613
127
6
130 198 270 345 422 503 587
152
7
150 228 308 389 472 556
178
8
171 259 346 433 519
203
9
194 290 384 476
229
9.5
206 306 404
241
222 445 667 890 1112 1334 1557 1779
SP
eed
(mm/sec)
THRUST (N)