Thermann Installer's Manual
Gas Continuous Flow Water Heaters
Water Piping
Please ensure this appliance does not receive inlet water greater than 85°C when used as a Solar booster.
Installation and service must be performed by a qualified plumber.
Observe all applicable codes.
This appliance is suitable for potable water applications. Do not use this appliance if any part has been
underwater. Immediately call a qualified service technician to inspect the appliance and replace any
part of the control system and gas control which has been under water.
Piping and components connected to the water heater shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.
A water heater used to supply potable water may not be connected to any heating system or
components previously used with a nonpotable water heating appliance.
When water is required in one part of the system at a higher temperature than in the rest of the
system, means such as a mixing valve shall be installed to temper the water to reduce the scald hazard.
• Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.
• Perform the following insulation measures for prevention of freezing.
• Take appropriate heat insulation measures (e.g., wrapping with
heat insulation materials, using electric heaters) according to
the climate of the region to prevent the pipe from freezing.
• Make sure that there are no water leaks from the cold and hot
water supply pipes, then insulate the pipes completely.
• Be sure to also completely insulate the water supply valve and
the cold and hot water connections on the water heater (refer
to the figure on the right).
• Do not cover the water drain plug with insulation so that water
in the pipe can be drained. (Refer to the figure in the right.)
• Use a union coupling for connecting the pipes to reduce the force applied to the piping.
• When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.
• Avoid using joints as much as possible to keep the piping simple.
• Avoid piping in which an air lock can occur.
• Use approved piping materials.
• If installing the unit on a roof (Above lower-level hot water supply):
If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure
supplied to the unit does not drop below 199 kPa. It may be necessary to install a pump system to
ensure that the water pressure is maintained at this level.
Check the pressure before putting the unit into operation.
Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit,
and may cause the unit to shut down frequently.
Completely insulate
the water inlet and
outlet fittings.
Insulate the water
supply valve completely.
Do not cover the water
drain plug with insulation
so that water in the pipe
can be drained.
Water inlet connections
• Pipe and fittings must meet the installation requirements of AS/NZS 3500.4 and local authority regulations.
• An isolating valve must be installed on the water inlet in close proximity to the heater.
• A GATE VALVE OR BALL VALVE must be used on the cold water inlet to the water heater. THIS
REQUIREMENT IS AN AUSTRALIA WIDE REQUIREMENT UNDER THE NATIONAL PLUMBING CODE.
STOP TAPS OR COMBINATION STOP TAPS AND NON-RETURN VALVES ARE NOT TO BE USED.
• The water heater needs a minimum water supply pressure of 200kPa to operate.
• Maximum water supply pressure must not exceed 800kPa : TH50ECR6, 1,000kPa : TH32ECR6
and TH28ENR6.
22
Summary of Contents for TH28ENR6L
Page 9: ...Component Details Example TH50ECR6 series model shown for illustration only Ex TH50ECR6 9 ...
Page 11: ...TH28ENR6 series model shown for illustration only Ex TH28ENR6 11 ...
Page 49: ...49 Memo ...
Page 50: ...Thermann Installer s Manual Gas Continuous Flow Water Heaters 50 Memo ...
Page 51: ...51 Memo ...
Page 52: ......