Set current control by external signal (Valid when pin No.7 of SW1 is on)
Function
Connection
terminal
Pin No.8
of SW1
Pin No.9
of SW1
Action
External voltage control
Pin No.7 to 8
of CN2
ON ON
External voltage 0V
→
10V
Set current 0A
→
Rated current
External resistance
control
Pin No.9 to 10
of CN2
ON OFF
External resistance 0
Ω
→
10k
Ω
Set current 0A
→
Rated current
Set voltage control by external signal (Valid when SW1
-④
is on)
Function
Connection
terminal
Pin No.5
of SW1
Pin No.6
of SW1
Action
External voltage control
Pin No.1 to 2
of CN2
OFF ON
External voltage 0V
→
10V
Set current 0A
→
Rated current
External resistance
control: Action I
Pin No.3 to 4
of CN2
ON OFF
External resistance 0
Ω
→
10k
Ω
Set current 0A
→
Rated current
External resistance
control: Action II
Pin No.5 to 6
of CN2
OFF OFF
External resistance 0
Ω
→
∞
Ω
Set current: Rated current
→
0A
◆
See
9-2-2. Adjusting the set voltage”
and
for details about how to set the internal voltage
and current.
If the IF-70PS has been installed in the unit, the pin No. of the connectors (CN1 and CN2) are arranged in the same way as
shown in the figure on the previous page.
CN 1 is the screw terminal for M3. Use a cable to which a round crimp-style terminal (inner diameter of at least 3.2mm)
is attached.
To wire CN 2, use the connector supplied with IF-70PS (Panasonic AXW120421 or Omron
XG5M-2035-N
)
・
Attach the AWG#24 - #28 cables (UL1007 stranded wire) to the terminal supplied with the IF-70PS, using a
single-wire caulking tool (Panasonic: AXY51000 or Omron: XY2B-7006).
・
Insert the cable (to which a terminal is attached) into the supplied connector.
64
64