![TEXIO PS-A Series Instruction Manual Download Page 20](http://html1.mh-extra.com/html/texio/ps-a-series/ps-a-series_instruction-manual_1097528020.webp)
11. A key (green/amber)
The current is set by operating this front panel key
・
Pressing this key causes it to turn off or light in green.
・
When the key is lit in green, it is possible to change the blinking digit of the set current in the current indicator.
・
Pressing and holding down this key switches the current display to the power display. Pressing and holding
down this key again switches the display back to the current display.
・
The key is lit in amber when the current is set by external analog signals.
12. MENU key (green)
Manual operation
・
Able to operate and confirm the MENU setting or selection when this key is lit in green.
・
Unable to configure the MENU setting when the output is on.
Sequence operation
・
This key lights in green when it is pressed, and the voltage and current indicators display the setting of the
sequence steps to be executed.
13. PROTECT key (green)
・
Pressing this key when it is turned off sets OVP (over-voltage protection).
・
When this key is lit, OVP (over-voltage protection), UVP (under-voltage protection), and OCP (over-current
protection) can be selected and set. Press the ESC key to finish setting the protections.
14. CHECK key (green)
Manual operation
・
When this key is lit, the voltage and current indicators display the set voltage and current. When it is not lit, the
indicators display the output voltage and current.
In the power indication, the voltage and current indicators display "- - - -".
・
Pressing this key displays the output voltage/current and the set voltage/current alternately.
Operate the MENU key to display the output voltage and current when the output is off.
Sequence operation
Changes the voltage and current indicators from the sequence steps to the output voltage and current, and vice
versa.
The sequence steps are displayed when this key is lit, and the output voltage and current are displayed when it is
not lit.
15. DIGIT KEY
▲
Manual operation
・
Pressing this key moves the digit of the set voltage, current, OVP, UVP, or OCP value to be changed to the left.
Sequence operation
・
Returns to the previous step while the sequence program is being executed.
・
If this key is pressed when execution is stopped, the execution STEP can be set to the START STEP (execution
mode: 0 and 1) and the END STEP (execution mode: 2 and 3) in the sequence program.
16. DIGIT KEY
▼
Manual operation
・
Pressing this key moves the digit of the set voltage, current, OVP, UVP, or OCP value to be changed to the right.
Sequence operation
・
Moves forward to the next step while the sequence program is being executed.
If this key is pressed when execution is stopped, the execution STEP can be set to the END STEP (execution
mode: 0 and 1) and the START STEP (execution mode: 2 and 3) in the sequence program.
10
10