![TEXIO PS-A Series Instruction Manual Download Page 24](http://html1.mh-extra.com/html/texio/ps-a-series/ps-a-series_instruction-manual_1097528024.webp)
33. AC inlet (400W and 800W models)
AC input terminal block (1200W models)
400W,800W model
1200W model
●
400W and 800W models
・
Use the supplied power cable. Connect the power cable to the AC outlet.
・
If the supplied power cable is used, the AC input voltage range of the unit will be
125V or lower (products for Japan only).
●
AC input terminal block (1200W models)
・
Use the supplied power cable. Connect the power cable to the distribution
panel. Be sure to attach the terminal cover to the terminal block after installing
the power cable.
・
Be sure to connect the power cable to the unit before connecting the power
cable to the distribution panel.
Supplying AC power to the unit that exceeds the specified input range may result in
failure, electric shock, or fire.
Performing wiring work while the power cable is connected to the AC outlet or
distribution panel may result in electric shock or fire.
For optimal air ventilation, maintain a distance of at least 30cm between the rear
panel and nearby objects.
If the rear panel is blocked, the internal temperature may rise.
34.
Protective grounding terminal
The product is equipped with a protective grounding terminal on the bottom face. For your own safety, make sure to
connect the unit to ground before use.
◆
See
“2-5. Connecting the protective grounding terminal on the bottom face”
for details.
Make sure to properly connect the protective grounding terminal on the bottom face.
Failure to do so may result in electric shock.
If you do not connect the protective grounding terminal on the bottom face, it will
come off from the CE conformity.
14
14