4 Transmitter
38
7.
Press
SET
and edit
Alarm delay
: Scroll one digit to the right
using
and increase value of digit by 1 using
(0 to 3600
seconds possible). Confirm with
SET
or abort entry with
ESC
.
8.
Return to
Channel x
with
ESC
.
9.
Return to
Alarm x
with
ESC
.
10.
Change to the other relays using
or
and perform settings
in the same way.
Using alarm as collective alarm or not using it at all
If an alarm is assigned to the collective alarm, the relay is switched
and a visual alarm can be issued via the display as soon as (at
least) one of the warning or error messages of the testo 6351
transmitter becomes active.
The messages affecting the collective alarm can only be
selected in the P2A software, see 5.3. Using the software.
✓
Alarm is selected (see previous steps 1 and 2).
1.
Use
or
to determine whether
Alarm x
should be used as a
Collective alarm
or
not used
. Confirm selection with
SET
.
2.
If collective alarm is selected: Select
Visual alarm
with
or
.
Select
YES
or
NO
with
or
. Confirm with
SET
and return to
Alarm x
.
3.
Change to another alarm using
or
and perform settings in
the same way.
4.
Return to
Main Menu Alarm
with
ESC
.
5. Continue to
Main Menu Settings
with
or
or return to
Measuring Mode with
ESC
.