5 Parameterizing, adjusting and analyzing software (P2A software)
61
Field
Explanation
Limit values, relay 1 to 4/alarm
values, alarm 1 to 4
In this mask, the relays or display
alarms are parameterized.
Relay x/alarm x
Four relays or alarm values are
available (optional).
Not used
Relay is not used.
Hysteresis image and input
options are hidden.
Collective alarm
A relay can be used as a collective
alarm detector in the event that
selected messages appear.
Selection of the messages (OR
linkage) by selecting the
checkbox.
Min control
If switched to ON (NO contact) or
OFF (NC contact) under the limit
value; in the event of a
subsequent exceeding of
Limit
value
plus
Hysteresis
, it is
switched to OFF (NO contact) or
ON (NC contact).
Max control
If switched to ON (NO contact) or
OFF (NC contact) above the limit
value; in the event of a
subsequent undershooting of
Limit value
minus
Hysteresis
, it
is switched to OFF (NO contact) or
ON (NC contact).
Summary of Contents for 6351
Page 2: ...2 ...
Page 33: ...4 Transmitter 33 4 4 5 Overview of the testo 6351 user menu ...
Page 34: ...4 Transmitter 34 ...
Page 35: ...4 Transmitter 35 ...
Page 84: ...0970 6353 en 03 ...