4 Transmitter
37
In addition, every alarm can be linked to a clearly visible visual
alarm (display background lighting and the corresponding
measurement value flash when limit values are violated).
An alarm delay between 0 and 3600 seconds can still be assigned
to every alarm used for limit value monitoring so that both the
corresponding relay effect and the visual alarm are delayed. If the
alarm status goes out within the set alarm delay time, neither the
visual alarm nor a relay connection is triggered. .
With an alarm status present, the visual alarm and all relay outputs
can be reset by means of acknowledgement with any button. The
triggering of a new alarm cannot be enabled until after the alarm
status goes out.
1.
In the Measuring Mode press
SET
, select
Main Menu Alarm
with
or
and confirm selection with
SET
.
- Four alarms can be parameterized.
2.
Select
Alarm x
with
or
and confirm selection with
SET
.
Using alarm to monitor limit values
NO contact
Monitoring minimum
Monitoring maximum
Hysteresis
Hysteresis
Limit value
Limit value
NC contact
Monitoring minimum
Monitoring maximum
Hysteresis
Hysteresis
Limit value
Limit value
3.
Select
Channel x
(e.g. "Channel 1") with
or
and confirm
selection with
SET
.
4.
Select
Max control
or
Min control
with
or
(see graphic).
5.
Press
SET
and edit
Limit value
as well as
Hysteresis
: Scroll
one digit to the right using
and increase value of digit by 1
using
. Confirm with
SET
or abort entry with
ESC
.
6.
Select
Visual alarm
with
or
. Select
YES
or
NO
with
or
. Confirm with
SET
or abort entry with
ESC
.
Summary of Contents for 6351
Page 2: ...2 ...
Page 33: ...4 Transmitter 33 4 4 5 Overview of the testo 6351 user menu ...
Page 34: ...4 Transmitter 34 ...
Page 35: ...4 Transmitter 35 ...
Page 84: ...0970 6353 en 03 ...