Example:
Standard Program –
Flow-Paced Sampling, Two Bottles Per Sample
This example shows you how to program the controller
to take flow-paced samples with the following settings:
The example displays are shown in the Normal
programming style.
•
Program type: Standard
•
Site description: Default
•
Bottle kit: 14, 950 milliliter bottles
•
Suction line length: 7 feet
•
Pacing: Flow pacing, every two pulses
•
Distribution: 2 bottles per sample
•
Sample Volume: 250 milliliters
•
Start time: Clock Time, 6:00
AM
on Monday,
Wednesday, Friday
•
Sampling duration: 24 hours
•
Module: No module installed
1. At the Main Menu, select PROGRAM and press
.
2. The option NO will be blinking. Press
.
3. Select the desired temperature units.
4. Select 14. Press
.
5. Type 950 and press
.
6. Type 7, then press
.
7. Select FLOW PACED, then, press
.
8. Enter the number of pulses between sample
events. Press
.
9. Select BOTTLES/SAMPLE.
10. Enter 2.
11. For this example, select NO to disable the Run
Continuously option. Selecting YES allows the
program to run indefinitely by repeating the sample
distribution and assumes that filled bottles are
replaced at regular service intervals.
12. Type 250. Then, press
.
Continued…
RUN
PROGRAM
VIEW REPORT
OTHER FUNCTIONS
SITE DESCRIPTION:
“FACTORY01“
CHANGE?
YES
NO
SELECT UNITS FOR
TEMPERATURE
°F
°C
NUMBER OF BOTTLES:
1
4
14
BOTTLE VOLUME IS
950
ml
(300-30000)
SUCTION LINE LENGTH
IS
7
ft
(3-99)
TIME PACED
FLOW PACED
FLOW BETWEEN
SAMPLE EVENTS:
2
PULSES (1-9999)
SEQUENTIAL
BOTTLES/SAMPLE
SAMPLES/BOTTLE
2
BOTTLES PER
SAMPLE EVENT (1-14)
RUN CONTINUOUSLY?
YES
NO
SAMPLE VOLUME:
250
ml (10-1000)
Summary of Contents for Everywhereyoulook BLZZRD
Page 2: ......
Page 4: ......
Page 8: ...BLZZRD Portable Refrigerated Sampler Safety vi ...
Page 16: ...BLZZRD Portable Refrigerated Sampler Table of Contents xiv ...
Page 34: ...BLZZRD Portable Refrigerated Sampler Section 1 Introduction 1 18 ...
Page 58: ...BLZZRD Portable Refrigerated Sampler Section 2 Installation Preparation 2 24 ...
Page 72: ...BLZZRD Portable Refrigerated Sampler Section 3 Programming Introduction 3 14 ...
Page 88: ...BLZZRD Portable Refrigerated Sampler Section 4 Standard Programming 4 16 ...
Page 219: ...BLZZRD Portable Refrigerated Sampler Appendix B Material Safety Data Sheets B 8 ...
Page 233: ...BLZZRD Portable Refrigerated Sampler Appendix D Replacement Parts D 6 ...
Page 241: ...BLZZRD Portable Refrigerated Sampler Appendix F Battery Selection Guide F 4 ...