background image

 92 

FAILURE

 LED (system output of this LED is set to 

«Generic «Failure») 

Status 

FAILURE

 LED

 

Onset Conditions 

No failures 

Lights 

green 

const. 

There are no system failures 

Failure 

Blinks

  yellow

  once  per 

second.  Pulse  duration 
0.5 sec 

There are failures in one or more assigned partitions

 

Sabotage 

Blinks

  yellow

  twice  per 

second.  Pulse  duration 
0.25 sec 

There  is  a  sabotage  (device  tampering  or  detachment  from  a 
wall) in one or more assigned partitions 

 

VIOLATION

 LED (system output of this LED is set to 

«Generic «Alarm/Violation») 

Status 

VIOLATION

 LED

 

Onset Conditions 

Not used 

Not lit 

No intrusion- / technological-type partitions assigned 

Ready / Not ready 

Blinks

 green

 once per 2 se-

conds. Pulse duration 0.25 
sec 

If at least one assigned intrusion- / technological-type parti-
tion is disarmed 

Armed 

Lights 

green

 const. 

All assigned partitions are armed. There is no violations. 

Violation / Alarm 

Blinks 

red 

 

If at least one assigned and armed partition is violated. 
Takes precedence over  

Ready 

Not ready 

and

 Armed 

statuses 

 

TEST

 LED (system output of this LED is set to 

«Generic «Test») 

Status 

TEST

 LED

 

Onset Conditions 

Test upon power up 

Lights up 

yellow

 for 20 s  Power up 

Standby mode 

Not lit 

No testing 

Test 

Lights 

yellow

 const. 

Testing detector is on 

 

FIRE DANGER

 LED (system output of this LED is set to 

«Generic «Fire Danger») 

Status 

FIRE DANNGER

 

LED

 

Onset Conditions 

Not used 

Not lit 

There are no partitions with double-event mode enabled 
and assigned to any LED 

Not ready 

Blinks

  green

  once  per  2 

seconds.  Pulse  duration 
0.25 sec 

Among partitions with double-event mode enabled and as-
signed to any LED(s) at least one is disarmed and has ‘Not 
Ready’ status 

Normal  

Lights 

green 

const. 

No 

Fire Danger 

detected  in assigned partitions with dou-

ble-event mode enabled 

Fire Danger 

Blinks 

red 

 

Fire Danger

 detected in one of the assigned partitions with 

double-event mode enabled 

Summary of Contents for ASTRA ZITADEL

Page 1: ...Research And Development Center TEKO ASTRA ZITADEL Wireless Intrusion and Fire Detection System QUICK START GUIDE...

Page 2: ...5 PRO STRUCTURE 17 6 WIRING RULES 18 7 MONITORING SOFTWARE SUITE ASTRA PRO GENERAL INFORMATION 30 8 GENERAL RECOMMENDATIONS FOR INSTALLERS 33 9 SYSTEM SETUP 38 10 MOUNTING DEVICES AT A SECURED FACILIT...

Page 3: ...3 15 EVENT LOG 72 16 SYSTEM USERS 75 17 LED INDICATION 85...

Page 4: ...ystem based on Astra 8945 Pro Control Panel version v1_x and Astra Pro Monitoring Software Suite MSS version v2_x Before you begin setting up your equipment we strongly recommend reading Chapters 1 8...

Page 5: ...The distinguishing feature of the wired part of the system is data exchange within random topology networks of TIA EIA 485 A RS 485 standard with improved driver parameters allowing over 100 component...

Page 6: ...o Frequency Wireless Channel WE Wireless Zones Extender WE 2 4 GHz Network Coordinator HE Hardwired Zones Extender Astra 713 RVZ Wireless Receiver Network Coordinator RB Rechargeable Battery AL Alarm...

Page 7: ...ector Astra Z 4345 RCKF or RC Remote Control Key Fob Astra Z 3245 RU Relay Unit Astra 823 WRU Wireless Relay Unit Astra 8245 LSA Light Sound Alerter Siren Astra Z 2345 FVA Fire Voice Alerter Astra Z 2...

Page 8: ...ystem control devices TM A unique 64 bit identification code in the Touch Memory interface input under the Dallas Semiconductor DS1990A R specification May come from electronic tablets iButton compone...

Page 9: ...arm Notification from an intrusion type device whose detection channel has a detectable physical factor Fire Alarm Notification from a fire type device whose detection channel has a detectable physica...

Page 10: ...olled voltage OC Open Collector output galvanically linked to the component s common wire Ensures control of inflowing current F VA Fire Voice Alerting PCB Printed Circuit Board BAT Battery ShC Short...

Page 11: ...maximum total capacity of up to 240 zones up to 250 logical partitions up to 500 system outputs located in various system components availability of system outputs Relay OC with circuit integrity supe...

Page 12: ..._1 is used as a hard wired zones extender 4 2 4 The Control Panel supports operation with Astra 823 and Astra Z 8245 relay units 4 2 5 Astra 8945 Pro Control Panel has 2 slots for installing and regis...

Page 13: ...ave several event sources The body of any device which reflects its operability status Its address is indicated in the MSS interface after For example MC 1 RTR 2 Detection channels channel 1 this is t...

Page 14: ...buttons 4 3 5 All events are divided into categories Categorization is performed on the basis of the Ademco Contact ID Protocol for Alarm System Communications SIA DC 05 1999 09 4 4 INFORMATION OUTPU...

Page 15: ...outers RTR detectors and alerters RTRs are intended to extend coverage range of the wireless network due to 16 levels of signal retransmission and increase communication stability between wireless dev...

Page 16: ...f universal outputs of A or B slot provided Astra RS 485 module is in stalled LAN interface implemented by means of universal outputs of A or B slot provid ed Astra LAN module is installed USB interfa...

Page 17: ...oved Delivery set of Control Panel includes whip antenna of 2 4 GHz frequency range which is connected to HF jack of embedded transceiver When installing antenna the cap of antenna insertion hole must...

Page 18: ...BE extenders SLV and SLV terminals Astra 8945 Pro Astra 814 Pro and Astra 863 ver A B have a special Zone input with current control terminated by a resistor of 3 9 kOhm to connect a relay output of a...

Page 19: ...0 27 V DC Power reservation is possible only by external power supply used Astra Z 8745 ver A supply voltage is 220 V AC possibility to install backup battery of LP704374 type delivered separately ins...

Page 20: ...SA Astra Z 2345 FLA Astra Z 2745 FVA Astra Z 2945 are powered from 2 lithium batteries of different types depending on device type Power reservation is provided by permanent battery charge control Bat...

Page 21: ...21 6 2 ASTRA 8945 PRO COMMON WIRING DIAGRAM...

Page 22: ...22 6 3 WIRING DIAGRAM FOR SYSTEM COMPONENTS...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...fore jumpers should be installed or removed with the device power turned off unless otherwise specified Plugs are intended for switching device to setup mode resetting device to default configuration...

Page 30: ...divided into three main program modules and two utilities 1 System Core This is the main MSS module Operates as a Windows Service and runs automatically at PC startup You can change some settings of t...

Page 31: ...in order to carry out equipment maintenance The Technician can arm disarm the system with its PIN Technician can login the system from any PC of the network on which MSS modules are installed as well...

Page 32: ...d RS 485 port Astra 984 adapter is used for physical connection not included LAN port provided Astra LAN module is installed not included EIA TIA 568B crossed type patch cord is used for connection to...

Page 33: ...ces are not strongly linked to each other and data transmission routs are built automatically within the network through several levels up to 16 of signal retransmission WE 433 network supports only o...

Page 34: ...ORK 433 MHZ Wireless zones extender WE 433 MHz supports up to 4 repeaters which are the same extenders WE 433 MHz switched to repeater mode Each wireless device of WE 433 MHz network is strongly linke...

Page 35: ...work coordinator or a detector and a router is approximately 15 20 meters with 2 dry walls of 1 brick thick partitions between rooms or one industrial reinforced concrete intermediate floor of up to 4...

Page 36: ...D as high as possible no lower than 2 m away of the floor as a rule at this height there are the fewest obstacles in rooms and this height also ensures normal functioning conditions for IR AC MC and S...

Page 37: ...ces and computer hardware antennas and radio fre quency tracts of communication devices including radio message transmitting systems etc Place wireless devices except the control panel keypad FCP wire...

Page 38: ...anel memory and recording required parameters into sysytem devices Stage 2 On site installation This stage is performed after the whole system operability test is completed 9 1 MSS SETUP MODULE Perfor...

Page 39: ...ess password for administration when it communicates with the DB The Engineer PIN is active in the Core until it is changed and recorded to the DB or recorded to the Control Panel memory which entails...

Page 40: ...utomatically 8 Perform initial setup change the Engineer PIN and record it to the device by clicking 9 Change all settings needed Thereafter all subsequent settings can be performed using the new pass...

Page 41: ...e registration is completed Status request of a group of devices cannot be performed The Setup Module is logged out only with the login PIN For more details refer to the integrated manual This Guide d...

Page 42: ...ity using any graphic editor Required file format Format BMP 32 bit Size no larger than 210x297 mm A4 Resolution max 100 120 dpi 2 Save BMP files to Monitor Pictures folder 3 Launch the Monitor with E...

Page 43: ...onitor depending on the complexity of the facility The tabs are be used to switch between graphic plans the plans are switched automatically during operation After a plan is added the Replace and Dele...

Page 44: ...nal clicks The location of any corner can be changed by clicking and dragging Partitions polygons may overlap or intersect In case of complete overlapping a pop up window appears to select necessary o...

Page 45: ...System Structure tab on the necessary position on the graphic plan The device icon will be added on selected place or click Add device button from the toolbox and select device type from a pop up win...

Page 46: ...nitor Images folder For example the Custom 1 icon s filename is pics_user1_14x14_9 bmp and its content is You can replace it with your own file with the same structure size in pixels and color gamma G...

Page 47: ...47 8 Re login the Monitor with Operator PIN by clicking The Monitor window will change Monitor setup is complete...

Page 48: ...reless devices again 1 First mount the Control Panel Astra 8945 Pro all hardwired devices and alarm loops cables Switch the power on 2 Perform sequential mounting of routers switching on the power sta...

Page 49: ...ace automatically 8 To optimize the communication of Astra Z 8145 Pro enter Engineer menu and choose Device Optimization submenu item for details refer to Astra Z 8145 Op eration Manual 9 For 433 MHz...

Page 50: ...munica tion quality details request command from the same right click menu 11 Build devices linkage map on the building floor plans for further analysis In case there are some non optimal links betwee...

Page 51: ...er using red button Make sure the Test message is displayed in the Monitor window for each device Test is available for all 2 4 GHz devices except Astra Z 3245 and for two 433 MHz devices Astra 4511 R...

Page 52: ...5 and for two 433 MHz devices Astra 4511 RF2 and As tra 421 RF2 1 Press the red button and irradiate LED of the device 2 Make sure the LED lights up red That means successful receipt of the command 3...

Page 53: ...s Devices tab of the Monitor interface by means of selecting necessary devices and choosing group testing request com mand from the right click menu For that purpose the Monitor Module must be logged...

Page 54: ...Setup Module interface when logged in with Engineer PIN 1 Testing of a system output is performed only in the absence of its assignment to a logical partition Therefore before starting the test it is...

Page 55: ...terface on the Voice Alerting tab 4 Right click on selected alerting area and select message to start by number or select message number in Start field 5 After the pre set delay min 30 sec the voice a...

Page 56: ...g area right click on selected message and choose Start voice alerting in the area com mand 9 Read alerting area status from the right click menu 10 Stop alerting from the right click menu 10 2 4 Test...

Page 57: ...5 to 10 seconds 3 After the process is completed Violation and Radio network LEDs are switched off Astra 713 1 Briefly close F1 plug for 1 to 2 seconds 2 Within 30 seconds press and hold the TMP butt...

Page 58: ...lt Settings Restoration Procedure resets all parameters to their default val ues deletes registered devices from the system and clears system event log Default configuration comprises two system acces...

Page 59: ...eted operability tests are done and system is put into operation It will allow you to easily replace the central Control Panel Astra 8945 Pro or wireless ex tenders WE 2 4 WE 433 later on for example...

Page 60: ...rmware files are stored in the Base folder For firmware update USB AM BM cable or Astra 984 adapter not included is used Wireless devices of 2 4 GHz networks are updated via Astra 985 interface not in...

Page 61: ...om F1 plug If Astra 8945 Pro firmware is updated without altering the firmware file generation e g version 1_0 is updated to 1_1 the device is ready for operation with same configuration If the device...

Page 62: ...out 4 Select WEM 2 4 in the Device tab 5 Further procedure is the same as for Astra 8945 Pro 13 2 3 WE 2 4 external wireless network coordinator 1 Switch off the power of the WE disconnect RS 485 int...

Page 63: ...2 4 Radio transceiver embedded into wireless extender WE 2 4 1 Power up WE 2 4 2 Connect WE to PC via USB 3 Run FW Update Module wait for the device descriptor to be read out 4 Select WE on the Devic...

Page 64: ...der Astra 713 doesn t support operat ing with Pro series Control Panels Therefore the device firmware must be neces sarily updated 13 2 6 Astra PSTN Module Astra RM Module Firmware update is not appli...

Page 65: ...to PC via USB 6 Further procedure is the same as for Astra 8945 Pro 13 2 9 ICP Astra 863 ver AE ICPE Astra 863 ver BE 1 Connect master devices IP Astra 863 ver A and IPE Astra 863 ver B with updat ed...

Page 66: ...P disconnect the device from RS 485 interface 2 While holding down the key switch power on 3 Connect HKP to PC via USB 4 Run FW Update Module wait for the devices descriptors to be read out 5 Select H...

Page 67: ...folder 1 Use the Add FW File To The Storage command from File menu of the FW Up date Module 2 Follow the update procedure for selected device General recommendations 1 We do not recommend updating fir...

Page 68: ...NEW DATABASE 1 Launch System Core Close Monitor and Setup Module on all PCs in case of network solution if opened 2 Run DB Manager enter Engineer password 3 Choose Create new command from Database me...

Page 69: ...eated Follow the procedure twice to create two databases Settings DB and Events DB Note New Settings Database is accessible with the default Engineer s PIN 123456 only New Settings Database doesn t co...

Page 70: ...Event DB only the actual password is not changed 14 2 DB BACKUP DB backup is used for further system event log analysis on a third party PC with SQL Server and MSS software installed 1 Choose DB Backu...

Page 71: ...71 3 Press OK Follow the procedure twice to create copy of Settings DB and Events DB 4 It is possible also to automatically backup databases on schedule This feature is available from Database menu...

Page 72: ...ts are copied and saved in Events Da tabase Note that Events DB unlike Control Panel s Event Log contains information not only about system events but also about user actions and MSS status That is th...

Page 73: ...73 3 Click Apply 4 Click Report icon to create a report...

Page 74: ...74 5 Click icon to create a list of events per shift...

Page 75: ...ECHNICIAN ENGINEER The difference between them consists in their system access permissions 16 1 USER PERMISSIONS partitions control by using PIN codes TM keys and remote control in accordance with aut...

Page 76: ...rom WKP HKP display in accord ance with PIN permissions system remote control from mobile phones provided the Astra GSM module is used 16 2 OPERATOR PERMISSIONS An Operator has the same permission as...

Page 77: ...displayed Partition control is also available from this window When an alarm event occurs the alarm processing buttons are activated for Intrusion alarm event Call detention group and Call for police...

Page 78: ...m event Call for fire reconnaissance group and Call for fire fighting group Actions available at an alarm event in fire type partitions Alarm confirmed Actions available at an alarm event in intrusion...

Page 79: ...any event in the lower field in the Partition current status field the ac tions undertaken by the Operator are displayed After complete processing alarm events can be moved to the Archive It is possib...

Page 80: ...cessing data are displayed in PDF formatted report issued from the Event Log window 1 Select group of events 2 Confirm group of alarms without speci fying reason and then move them to archive Alarm ar...

Page 81: ...and then apply the TM key once again within 30 sec to confirm the command If more than 30 seconds have passed after the last button has been pressed the command is cancelled automat ically 3 An Opera...

Page 82: ...ntrol logical parti tions and alerting sub system from HKP Astra 814 Pro or WKP Astra 8145 Pro menu in accordance with his PIN permissions for details see HKP WKP Operation Manual A Technician is allo...

Page 83: ...gin the MSS Setup Module to fully configure the sys tem 2 An Engineer is allowed to login the MSS DB Manager to change settings of actual databases or create new databases see paragraph 14 3 An Engine...

Page 84: ...sions connected with the port occupancy For this purpose the Monitor Module already has the possibility to change port number in the Number of the network port on a computer running the system core fi...

Page 85: ...age is normal Backup power supply disconnected or voltage is below normal Power failure Blinks yellow once per second Pulse duration is 0 5 sec Main power supply disconnected or voltage is below norma...

Page 86: ...installed into Slot POWER LED Status POWER LED Onset Conditions Power normal Lights green const Main power supply is present voltage is normal Backup power supply is present voltage is normal Switch...

Page 87: ...e per second Pulse duration is 0 5 sec Supply voltage is below normal from 11 5 to 10 2 V Fast blinking red in sync with the indicators 1 8 Supply below 10 2 V inoperability status Status LED 1 8 Onse...

Page 88: ...ation with Control Panel All blink red synchronously No data exchange via RS 485 interface due to interface failure Not registered Not lit Relay Unit is not registered or registration data are cleared...

Page 89: ...ted or open circuited FAILURE LED system output of this LED is set to Generic Failure Status FAILURE LED Onset Conditions No failures Lights green const There are no system failures Failure Blinks yel...

Page 90: ...ready status Normal Lights green const No Fire Danger detected in assigned partitions with dou ble event mode enabled Fire Danger Blinks red Fire Danger detected in one of the assigned partitions wit...

Page 91: ...reen during 10 seconds When testing devices in partitions 17 6 HARDWIRED KEYPAD ASTRA 814 PRO POWER LED Status POWER LED Onset Conditions Power normal Lights green const Main power supply is present v...

Page 92: ...ons are armed There is no violations Violation Alarm Blinks red If at least one assigned and armed partition is violated Takes precedence over Ready Not ready and Armed statuses TEST LED system output...

Page 93: ...ed partitions In current system version SYSTEMS START SYSTEMS ON SYSTEMS STOP LEDs are not enabled 17 7 DISPLAYING SYSTEM STATUS BY WKP ASTRA 8145 PRO AND HKP ASTRA 814 PRO In On Duty mode in the abse...

Page 94: ...nuals A quick way to check malfunctions and sabotages without Operator s permissions is not provided Sales Controlex GmbH Warranty service and technical support TD Philosophenweg 31 33 47051 Duisburg...

Reviews: