54
During testing the detectors, having received the command over the radio, switch on their
indicators for the time of 10 seconds, perform the test and send the results to the Control
Panel. The test progress is displayed in
Mark about passing the test
and
Date/ Time
columns.
Test results in a form of a relative value of dust, expressed in % for SD detectors, and ac-
tual temperature C
º of the ambient air for HD detectors are displayed in the Dust Lev-
el/Temperature column. Test results are logged.
10.2.2.
System outputs testing is available only from the Setup Module interface when
logged in with
Engineer
PIN.
1)
Testing of a system output is performed only in the absence of its assignment to a
logical partition. Therefore, before starting the test it is necessary to de-assign it
from a partition and record settings into the Control Panel, and at the end of the
test - to restore assignment and record settings into the PPKOP again.
2)
Right-click on selected output and choose
Switch ON
or
Switch OFF
command.
3)
Check the output status visually (for LSA and FLA) or by a multimeter.
10.2.3.
Testing the voice alerting (including test messages) in any alerting area is availa-
ble from the
Monitor
interface when it is run with
Technician
or
Operator
PIN.
When testing, de-assign
relay output from all par-
titions
Summary of Contents for ASTRA ZITADEL
Page 3: ...3 15 EVENT LOG 72 16 SYSTEM USERS 75 17 LED INDICATION 85...
Page 21: ...21 6 2 ASTRA 8945 PRO COMMON WIRING DIAGRAM...
Page 22: ...22 6 3 WIRING DIAGRAM FOR SYSTEM COMPONENTS...
Page 23: ...23...
Page 24: ...24...
Page 25: ...25...
Page 26: ...26...
Page 27: ...27...
Page 28: ...28...
Page 73: ...73 3 Click Apply 4 Click Report icon to create a report...
Page 74: ...74 5 Click icon to create a list of events per shift...