88
17.4 RELAY UNIT ASTRA-823
LED
Status
LED
« »
Onset Conditions
Power normal
Lights
green
const.
Supply voltage is normal, from 11 to 15.5 V
Power failure
Blinks
red
Supply voltage is below normal, from 11 to 10.3 V
Not lit
Supply voltage is below 10.3 V (failure status)
LED
«
1
», «
2
», «
3
» and «
4
»
Status
LED
Onset Conditions
«1» / «2»
«3» / «4»
No communication
with Control Panel
All blink
red
synchronously
No data exchange via RS-485 interface
due to interface failure
Not registered
Not lit
Relay Unit is not registered or registration
data are cleared as a result of device reset
to default settings
Relay open
Blink
green
-
Load circuit integrity supervision
Relay closed
Light
green
const.
-
Load circuit shorting
Blink
green
-
Any state of relay
Load circuit cut
Light
red
const.
-
Relay open
Light
red
const.
Blink
green
AC/DC 250 V circuit switching
Relay closed
Light
red
Light
green
Summary of Contents for ASTRA ZITADEL
Page 3: ...3 15 EVENT LOG 72 16 SYSTEM USERS 75 17 LED INDICATION 85...
Page 21: ...21 6 2 ASTRA 8945 PRO COMMON WIRING DIAGRAM...
Page 22: ...22 6 3 WIRING DIAGRAM FOR SYSTEM COMPONENTS...
Page 23: ...23...
Page 24: ...24...
Page 25: ...25...
Page 26: ...26...
Page 27: ...27...
Page 28: ...28...
Page 73: ...73 3 Click Apply 4 Click Report icon to create a report...
Page 74: ...74 5 Click icon to create a list of events per shift...