90
TEST
LED (system output of this LED is set to
«Generic «Test»)
Status
TEST
LED
Onset Conditions
Standby mode
Not lit
Test is not performed
Test
Lights
yellow
const.
Test of LEDs and functionality is performed
FIRE DANGER
LED (system output of this LED is set to
«Generic «Fire Danger»)
Status
FIRE DANNGER
LED
Onset Conditions
Not used
Not lit
There are no partitions with double-event mode enabled
and assigned to any LED
Not ready
Blinks
green
once per 2
seconds. Pulse duration
0.25 sec
Among partitions with double-event mode enabled and as-
signed to any LED(s) at least one is disarmed and has ‘not
ready’ status
Normal
Lights
green
const.
No
Fire Danger
detected in assigned partitions with dou-
ble-event mode enabled
Fire Danger
Blinks
red
Fire Danger
detected in one of the assigned partitions with
double-event mode enabled
FIRE ALARM
LED (system output of this LED is set to
«Generic «Fire Alarm»)
Status
FIRE ALARM
LED
Onset Conditions
Not used
Not lit
There are no partitions assigned to any LED
Not ready
Blinks
green
once per 2
seconds. Pulse duration
0.25 sec
Among partitions assigned to any LED(s) at least one is
disarmed and has ‘not ready’ status
Normal
Lights
green
const.
No
Fire Alarm
detected in assigned partitions
Fire Alarm
Lights
red
const.
Fire Alarm
detected in one of the assigned partitions
In current system version
«
SYSTEMS START
», «
SYSTEMS ON
» и «
SYSTEMS STOP
»
LEDs are not enabled.
Summary of Contents for ASTRA ZITADEL
Page 3: ...3 15 EVENT LOG 72 16 SYSTEM USERS 75 17 LED INDICATION 85...
Page 21: ...21 6 2 ASTRA 8945 PRO COMMON WIRING DIAGRAM...
Page 22: ...22 6 3 WIRING DIAGRAM FOR SYSTEM COMPONENTS...
Page 23: ...23...
Page 24: ...24...
Page 25: ...25...
Page 26: ...26...
Page 27: ...27...
Page 28: ...28...
Page 73: ...73 3 Click Apply 4 Click Report icon to create a report...
Page 74: ...74 5 Click icon to create a list of events per shift...